Owner's Manual

PRINTED IN USA PAGE 1 OF 2
RA-4410RC
REMOTE ANNUNCIATOR
MFG# 5401175 - REV E
1/16
Potter Electric Signal Company, LLC • St. Louis, MO • Cust. Service: 866-572-3005 • Tech. Support: 866-956-0988 • Canada 888-882-1833
www.pottersignal.com
Operation
The RA-4410RC remote annunciator is designed to operate with the
PFC-4410RC releasing control panel. The unit mounts to a 4 gang
box. There are 34 LED's to indicate a change in panel status. There is
a buzzer on the annunciator that sounds for any trouble or supervisory
condition. Pressing the LAMP TEST button illuminates all of the
lamps. The release panel supervises and communicates with the
annunciator via separate connections for the RS-485 communication
and the 24VDC power requirements of the RA-4410RC. Separate
cables should be used for power and communication. Shielded cable
must be used for the communication line. Up to four annunciators can
be connected to one panel. A Rotary switch is provided on the panel to
indicate how many annunciators are connected. Another rotary switch
is on the annunciator to set the address. The annunciators must be
addressed consecutively.
Architect/Engineers Specications
The Annunciator for the extinguishing agent release panel shall be a
microprocessor based device. The unit shall require 24vdc operating
voltage and a shielded RS-485 connection for communication; both
supplied by the release panel. The annunciator shall have a rotary
UL, cUL, & CSFM Listed, FM Approved, MEA Accepted
Dimensions:
8-1/4" W x 4-1/2" H x 1" D (Approximate)
Enclosure:
Stainless steel plate with clear plastic shield protecting zone
and output identication labels.
Mounts in 4 gang box.
For surface mounting use back box stk# 3006401
Environmental Specications:
Indoor use only
Temperature range 32°F to 120°F (0°C to 49°C)
93% Humidity
Electrical Requirements:
24VDC 10 mA standby/ 13 mA alarm / 26 mA max. (lamp test)
RS-485 Communication: (Two wire Shielded cable required).
Ground drain wire to S terminal on PFC-4410RC Panel only.
Max. Distance: 2000 ft. using 22 ga. wire and 4000 ft. using 20 ga. wire.
Stock number: 3006400
switch to set the address number of that annunciator to allow for
supervision by the panel. The annunciator shall have indicators for
Alarm, Trouble, and Supervisory per zone, Output circuits active,
Output circuit troubles, AC power, Power trouble, Supervisory
condition, Supervisory trouble, Abort, System trouble, Alarm silence,
Ground fault, Abort, Pre-discharging/Discharged. In addition to
the visual indicators there shall also be a buzzer that sounds on any
trouble or supervisory condition and a button to test the indicators.
Features
• Up to 4 annunciators can be connected to one PFC-4410RC
• Rotary switches on panel and annunciator for supervisory purposes
• Trouble/Supervisory buzzer
Separate LED's for: Alarm and Trouble per zone, Outputs activated
or in trouble, Supervisory, Abort, Supervisory trouble, Power trouble,
System trouble, Alarm silence, Ground fault, Discharging/Discharged
• Lamp test switch
• Slide in Zone & Output identication labels