Instructions
PVX 100M
Mass Notification System
SN2
1 = OFF 8 sec. initial delay
2 = ON
3 = OFF
4 = ON 8 sec. repeat delay
5 = OFF
6 = ON Message On
7 = OFF 3 Repeats
8 = ON
FACTORY DEFAULT SWITCH SETTINGS:
SN1
1 = OFF Temporal Whoop Signal
2 = X Do not use
3 = X Do not use
4 = Fault Code Lock
5 = X Do not use
6 = AC Fault Delay
7 = ON Battery connected
8 = ON Mic connected
1 8
ON
OFF
Switch Network Detail
P/N 1-5001M R3.14
SN1
SN2
P8
P4
LED 4
LED 5
1
2
3
4
5
6
7
TB5
P9
S1
TB5: PVC-RMI
TER 1:
2:
3:
4:
5:
6:
(NOTE 2, 4, 6)
Circuit Neg
TER +24VDC (0.5A)
TER Audio -
TER Audio +
TER RS 485 -
TER RS 485 +
TER 7: No Connection
P8: I2C Port
10 Pin Connector
PVC-ZM/SL8/IL8/OL8
All other terminals are identical to the PVC-100 Module.
Please refer to P/N 1-5001 R2.14 for full installation
Instructions and ratings
PVX 100M
PVX 200M
1) Speaker Circuits
2) Speaker Circuitsand 1) PVC-100E
Contains 1) PVC-100M
Contains 1) PVC-100M
The PVX 100M Mass Notification System is functionally identical to the PVX 100 with the exception of an Intelligent Interface for an LOC.
The PVX 100M may be used as an ACU and combined with accessory modules to meet the requirements of UL2572. The system system
provides a Physical and Communication Security Level 1, Audit Control Level 2, Stored Data and Access Control Security Level 0 per UL
2572 Mass Notification Standard. The system is designed to be used in conjunction with a UL listed Fire Alarm Control Panel (FACP) to
provide a Listed Voice Evacuation Alarm System with Mass Notification capabilities.
The FACP provides all Fire initiating circuitry and a signaling circuit to the PVX 100M. The PVX 100M provides its own internal
supervision as well as supervision for its speaker lines and accessories. Any fault is reported back to the FACP. In normal standby the
supervisory circuit from the panel is connected to a matching EOLR. Should the PVX 100M suffer an internal failure or should there be any
fault on the speaker line or accessory a contact would open and the FACP would report it as an open fault for that circuit.
The PVX 100M is designed to be powered from 120 VAC at 60 Hz and will provide 100W of audio. Speakers may be 25 or 70 Vrms (jumper
selected, 25V is factory set). See Installation Instruction P/N PVX 25-50-100 R2.14 for all Electrical Specifications, Standard Terminal
Designations and Wiring Diagrams.
MODELS: The PVC-100M is a complete Voice Evac/MNS Module, it is complete with built-in tones and messages for Fire and MNS. The
PVC-100M may be coupled with additional PVC-100E Expander modules for systems requiring greater power.
The PVX 100M and PVX 200M are complete Voice Evacuation Panels. Where greater Audio power is required they meay be combined with
Expander panels, PVX 100E/200E/300E/400E/500E/600E. When using any EVX Expander Module, refer to installation instructions P/N 1-
5002 R2.14.
Note: All Switch settings refer to Fire Tone/Message only.
All MNS Tone/Messages must be Pre-Configured for System.
MNS Tone/Messages will play continuous until reset.
For technical assistance please call:
866-956-1211
5757 Phantom Dr. St. Louis, Missouri 63042
www.pottersignal.com