Owner's Manual

8830079 - REV D 12/18 PAGE 2 OF 2
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
PAD100-MIM
Micro Input Module
Setting the Address
Wiring Diagram
Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the front of the PAD100-MIM. Before
connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Fig 1
Model Description Stock No.
PAD100-MIM
Micro Input Module
3992700
Ordering Information
FROM FACP OR PREVIOUS
DEVICE AND TO NEXT DEVICE
TO NORMALLY OPEN
MONITORED DEVICE
5.1K OHM REQUIRED
Part #3005013
firealarmresources.com