Instruction Manual

78
PFC-9000 • 5403535 • REV G • 9/08
HARDWIRE DETECTION ADDER MODULE (ZA-9008)
- 8 supervised Style B (Class B) or 4 Style D (Class A) Initiating Circuits; fully congurable. Terminals are labeled “INI”.
Initiating Circuits are Compatibility ID “A”.
Power Limited: 22VDC, 3 mA standby, 5mV ripple, 50 mA max. (alarm)
- Current Consumption: Standby: 80 mA, Alarm: 100 mA
HARDWIRE SIGNAL ADDER MODULE (IDC-9004)
- 4 Style Y or Z (Class B or A) Notication Circuits; congurable as strobes or audibles.
Terminals are labeled “IND”.
Power Limited: 24 VDC unltered 1.25 A @ 49°C per Circuit
- Current Consumption: Standby: 35 mA, Alarm: 150 mA
HARDWIRE RELAY ADDER MODULE (ARM-9008) (resistive loads)
- Must be connected to a Listed Power Limited Source of Supply. Terminals are labeled “RLY”.
- 8 fully Congurable Form C Relays.
Form C, 1 Amp., 28 VDC (resistive loads)
- Current Consumption: Standby: 25 mA, Alarm: 150 mA
POLARITY REVERSAL AND CITY TIE MODULE (PR-5000)
- Supervised City Tie Not Power Limited
24VDC unltered, 210 mA max., Trip coil: 14 ohms.
Terminals are labeled “City Tie”.
- Polarity Reversal Power Limited
Terminals are labeled “Polarity Reversal”.
24VDC open
12VDC @ 3.5 mA, 8 mA max. (shorted)
- Current Consumption: Standby: 35 mA, Alarm: 300 mA
System Model: SERIES PFC-9000, Fire Alarm Control Panel
System Type: Local, Auxiliary (using PR-5000), Remote Protected Premise Station (using PR-5000 or
UDACT-9100), Central Station Protected Premises (using DACT-5000 or UDACT-9100)
Type of Service: A, M, WF, SS (with UDACT-9100)
Type of Signalling: Non-Coded
Applicable Standards: NFPA 70 and 72, UL-864, ULC S-524, ULC S-527.