Instruction Manual

6
PFC-9000 • 5403535 • REV G • 9/08
CHAPTER 1 INTRODUCTION
This manual is designed to help with the specication, design and installation of the Potter PFC-9000 series re alarm control
panel. It is imperative that the manual be completely read and understood before beginning the installation of the re alarm
panel. The manual is broken down to give an overview of components and ordering information, installation guidelines and
programming directions. Only qualied individuals should install the re alarm panel and check the integrity of the installation
and programming.
General Description
The PFC-9000 series re alarm control panels are listed, microprocessor based, analog/addressable systems that allow for very
exible applications for use in mid sized addressable applications. The panel and the sensors communicate giving the user the
address, location and level of alarm status utilizing a Signaling Line Circuit (SLC). The system offers a wide variety of modules
and features that allow for even the most difcult applications. The panel has a powerful 12 amps power supply, 10 amps which
are available for notication circuits.
The PFC-9000 base panel consists of one intelligent analog SLC loop capable of supporting 127 analog/addressable sensors and
addressable modules which can be wired in Class A (Style 6 or 7) or Class B (Style 4). The system may be expanded to three
loops using the loop expansion cards, bringing the system to a total of 381 addressable points.
The Main Display has a large 4 line 20 character alphanumeric LCD display and the common indicators with LED’s. The PFC-
9000 utilizes a simple menu system with a keypad to operate commands in the system.
In addition the base panel supports 3 adder circuit cards that provide a wide variety of features. Each of the Conventional
Hardwire Circuit adder modules allow for eight Class B (Style 4) circuits or four Class A (Style 6 or 7) circuits. The Notication
Hardwire Circuit adder module provides four additional notication circuits, each rated at 1.7 amps each in addition to the
base panel four notication circuits. The Relay Hardwire Circuit provides eight fully congurable form C contacts that may be
correlated to any input of the system.
The PFC-9000 series re alarm control panel offers three methods for communicating a re alarm to the proper authorities; the
Polarity Reversal/City Tie Connection, the form C alarm relay and a digital communicator.
System Features
• 127 Addressable Points per Loop which can be wired Class A or Class B
Up to Three Loops per Panel – 381 Points
Any Combination of Sensors and Modules
Four Notication Circuits rated at 1.7 Amps each
Up to 10 amps available to Notication Circuits
Multiple Audible tones available; Steady, Temporal Code, California Code, March Time
Silent or Audible Walk Test Feature
1000 Alarm History Buffer
2000 All Event History Buffer
Resettable output for Four Wire Smoke Detector Power
Three Levels of Password Protection
RS-485 Interface for Remote Annunciators
RS-232 Port for CRT or Printer
Surface or Flush Mount Cabinet with Removable Door
Removable Terminal Blocks
Smoke Sensor Sensitivity Selection Drift Compensation
Form C Contacts for Common Alarm, Trouble and Supervisory Conditions
Front Panel Auto Congure/ Computer Based User Conguration
Loop, Circuit, Zone or Device Bypass
Large LCD Display
Automatic or Manual Signal Silence
• Selectable Two-Stage Operation
Failure to read and understand these directions may result in system malfunction or operation as not intended. Further, installers
should be trained on the PFC-9000 system as well as meet the minimum requirements of NFPA 72 National Fire Alarm Code.