Instruction Manual

42
PFC-9000 • 5403535 • REV G • 9/08
S (IN)
24+ (OUT)
SOM-4
24- (OUT)
24+ (IN)
24- (IN)
OUT ( + )
OUT ( - )
SC (IN)
S (OUT)
SC (OUT)
FROM PFC-9000
TO NEXT
DEVICE
10K EOL
DWG# PFC-9000-29A
All wiring shown
is supervised and
inherently power
limited.
UL Listed regulated,
power limited supply
for re protection
signaling service for
audible devices.
DRM Relay Module
The DRM is a relay module that is controlled by the re alarm panel and correlated to the inputs of the system. The DRM has two
independent form C relays that activate simultaneously. Both relays must be wired either power limited or non-power limited.
When the device is activated the red LED will latch on and the relays will change position. When the device is being polled the
LED will ash. Contacts are rated 2 Amps at 30 VDC.
Use only FPL, FPLR, or FPLP wiring in accordance with Article 760 of the National Electrical Code.
S (IN)
NO1
DRM-4
COM1
NC1
NO2
COM2
NC2
SC (IN)
S (OUT)
SC (OUT)
FROM PFC-9000
TO NEXT
DEVICE
DWG# PFC-9000-29B
All wiring shown
is supervised and
inherently power
limited.
(FORM “C”
CONTACTS NON-
SUPERVISED)
SET 2
SET 1
All wiring shown on contact
terminals are shown in standby
mode.
Inputs to both sets of Form “C” contacts must be either Power Limited or Non-Power Limited. Do not mix Power Limited
wiring with Non-Power Limited wiring on contact side.
Notication Appliance Circuit (NAC)
NAC installation wiring shall not exceed 50 Ohms