Instruction Manual
40
PFC-9000 • 5403535 • REV G • 9/08
ADSD Duct Smoke Detector
The ADSD is the duct smoke detector designed to easily mount on the side of an HVAC duct and monitor for smoke conditions
in the duct. A template and mounting hardware is provided with the unit for mounting. The device mounts without the removal of
the outer cover. The devices are designed to operate without screens and lters, therefore the amount of maintenance needed for
the device is minimal. The re alarm panel controls the sensitivity of the smoke sensor.
Both the ADSD-P and ADSD-PR utilize a photoelectric smoke sensor. The ADSD-P has four terminals, two for the SLC loop and
two for remote output of an LED. The ADSD-PR has terminals for two form C relays that are rated for 10 amps at 125/250 VAC.
The ADSD-PR requires 24 VDC to operate. Failure to provide 24 VDC power will result in the panel showing a missing device.
The ADSD will monitor airow between 300 and 4,000 feet per minute and require that the user purchase air-sampling tubes in
order to achieve proper airow through the unit. Sampling tubes are available in 3, 5 and 10-foot lengths.
THE ADSD-P AND ADSD-PR ARE NOT SELF-
CONTAINED SENSORS. THIS PRODUCT IS
COMPATIBLE ONLY WITH FIRE ALARM
CONTROL PANELS THA T UTILIZE HOCHIKI’S
DIGITA L COMMUNICATIONS PROTOCOL,
DCP. FOR EXAMPLE, THE POTTER PFC-9000.
ADSD-P
REMOTE LED WIRING MUST
HAVE POLARITY AS SHOWN
(24 VDC 8mA MAX)
S
SC
UL LISTED
CONTROL PANEL
LOOP INTERFACE
TO NEXT
SENSOR
DWG# PFC-9000-26A
L1 L2 L3 L4
1
234
ADSD-P Wiring Diagram
The ADSD is addressed in one of two ways and both require the removal of the cover to access the smoke head. The head can be
removed and inserted on the hand held programmer and addressed like all of the other sensors. The other option is to use the FRCM-2
cable and connect to the SLC terminal strip on the ADSD. The programming of the device is the same as if it was connected.
ADSD-PR Wiring Diagram
UL LISTED
CONTROL PANEL
ADDRESSABLE
LOOP
OBSERVE POLARITY
INPUT VOLTAGE 24 VDC 10mA
STANDBY 55mA ALARM
REMOTE
ALARM
LED
SUPPLY VOLTAGE
FAN
ALARM CONTACTS 10A
NO
C
NC
NO
C
NC
ALARM CONTACTS 10A
TO NEXT SENSOR OR
RETURN TO CONTROL
PANEL
ANALOG ADDRESSABLE FIELD
LOOP WIRING
TERMINATE REMOTE ACCESSORIES AS INDICATED ABOVE (IF REQUIRED). THIS IS NOT A
SELF-CONTAINED STAND ALONE DETECTOR. A UL LISTED ANALOG ADDRESSABLE FIRE
SYSTEM IS REQUIRED.
DWG# PFC-9000-26B
REMOTE
PILOT LED
REMOTE
TEST
SWITCH
LOOP INTERFACE
S
SC
12 34
5 6
7
8910 11 12