Instruction Manual

29
PFC-9000 • 5403535 • REV G • 9/08
Notication Circuits Wire Terminations
Main Board Notication Circuits are rated for 1.7 Amps each,IDC-9004 Notication Circuits are rated for 1.7 Amps each.
NOTE : MAXIMUM VOLTAGE DROP SHOULD NOT EXCEED 1.8 VOLTS AND THIS TABLE ASSUMES TOTAL LOAD AT
END OF THE LINE
Notication Appliance Wiring Chart
LATOT
DAOLLANGIS
)RLE(ECIVEDTSALOTNURGNIRIWMUMIXAM
POOL.XAM
ECNATSISER
GWA81GWA61GWA41GWA21
spmAtfmtfmtfmtfm smhO
60.0053261705733411000692810058195203
21.00811063058176500035190524962151
03.0074341057922002166300919756
06.0532175734110063810589523
09.065174052670042210754712
02.18116358165003195249215.1
05.1499205164042373435012.1
07.187425218300216582780.1
Field Wiring Terminals
A TOTAL OF 10 AMPS POWER AT 24
VDC UNFILTERED ON 8 CIRCUITS.
(WITH IDC-9004 INSTALLED)
CLASS B
(STYLE Y)
CLASS A
(STYLE Z)
3.9k EOLR
IND 1IND 2
IND 3IND 4
DWG# PFC-9000-39
Note:
All devices must be wired either
Class A or Class B.
Refer to IDC-9004 bulletin for
settings.
The combination of Class A and B
wiring shown is for demonstration
purposes only.