PFC-9000 • 5403535 • REV G • 9/08
Notication Circuits Wire Terminations
Main Board Notication Circuits are rated for 1.7 Amps each,IDC-9004 Notication Circuits are rated for 1.7 Amps each.
NOTE : MAXIMUM VOLTAGE DROP SHOULD NOT EXCEED 1.8 VOLTS AND THIS TABLE ASSUMES TOTAL LOAD AT
END OF THE LINE
Notication Appliance Wiring Chart
LATOT
DAOLLANGIS
)RLE(ECIVEDTSALOTNURGNIRIWMUMIXAM
POOL.XAM
ECNATSISER
GWA81GWA61GWA41GWA21
spmAtfmtfmtfmtfm smhO
60.0053261705733411000692810058195203
21.00811063058176500035190524962151
03.0074341057922002166300919756
06.0532175734110063810589523
09.065174052670042210754712
02.18116358165003195249215.1
05.1499205164042373435012.1
07.187425218300216582780.1
Field Wiring Terminals
A TOTAL OF 10 AMPS POWER AT 24
VDC UNFILTERED ON 8 CIRCUITS.
(WITH IDC-9004 INSTALLED)
CLASS B
(STYLE Y)
CLASS A
(STYLE Z)
3.9k EOLR
IND 1IND 2
IND 3IND 4
DWG# PFC-9000-39
Note:
All devices must be wired either
Class A or Class B.
Refer to IDC-9004 bulletin for
settings.
The combination of Class A and B
wiring shown is for demonstration
purposes only.