Instruction Manual

11
PFC-9000 • 5403535 • REV G • 9/08
Field Wiring Terminations
Below is the terminal list from left to right as they appear on the main FACP board. All terminals are removable and are power
limited. The relays are rated for 28 VDC at 1 Amp.
RS485 #1
S
TROUBLE
ALARM
SUP LOOP4W SUP AUX PWR
RT I
COM
COM
COM
COM(-)
NO
NO
NO
NC
NC
NC
B
A
IND CKT 1
IND1 +
CLASS B CLASS A
3.9 K 3.9 K
IND CKT 2 IND CKT 3 IND CKT 4
IND1 +
IND1 -
IND1 -
IND2 +
IND2 +
IND2 -
IND2 -
IND3 +
IND3 +
IND3 -
IND3 -
IND4 +
IND4 +
IND4 -
IND4 +
DWG# PFC-9000-33
Terminal Denitions
RS485#1 RS-485 communication connection for the Remote Annunciators
Trouble Form C relay that activates upon any trouble condition
Alarm Form C relay that activates upon any alarm condition
Sup Form C relay that activates upon any supervisory condition
Loop (B) Terminals for wiring a Class B SLC loop
Loop (A) Terminal for wiring a Class A SLC loop, + - (out) + - (return)
4W Sup Four Wire Smoke Detector Power (+ left, - right)
AUX PWR 24 volts DC at 1.7 Amps Auxiliary Power (+ left, - right)
RTI Remote Trouble Indicator (+ left, - right)
IND CKT 1 First Notication Circuit (Loop 0, Address 0)
IND CKT 2 Second Notication Circuit (Loop 0, Address 1)
IND CKT 3 Third Notication Circuit (Loop 0, Address 2)
IND CKT 4 Fourth Notication Circuit (Loop 0, Address 3)
Wire all Class A or Class B.
Do not mix.
This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing
device pursuant to Subpart J of Part 15 of FCC Rules which are designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which
case the user at his own expense will be required to take whatever measures may be required to correct the interference.