PFC-9000 Fire Alarm Main Board Connections
Jumpers
JW 1 - Used when a PR-5000 or UDACT-9100 is installed. Remove the jumper any time one of these devices is added.
JW 2 - For factory programming only, not for eld use, DO NOT MODIFY
JW 3 - For factory programming only, not for eld use, DO NOT MODIFY
JW 4 - For factory programming only, not for eld use, DO NOT MODIFY
Plug Connections
P1 - Not Used
P2 - RS-485 connection for computer programming connection
P3 - Not Used
P4 - Port for connecting PR-5000 or UDACT-9100
P5 - Loop Adder connection port
P6 - Circuit adder card communication connection
P7 - Factory use only
P8 - Power connection for adder cards
P9 - RS-232 connection for printer or CRT
P10&11 - Power connection to bridge rectifer
P12&13 - Connection for 24VDC batteries
P14 - Connection for LCD display board F1 – 20 Amp AGC or equivalent battery fuse
P1
P2
FIELD WIRING TERMINALS
P3
P5
P6
P8
P4
JW1
P14
JW3
JW2
JW4P7P9
P10 P11 +BDG- P12 P13 +BDG-
MAIN FIRE ALARM BOARD
DWG# PFC-9000-13
F1