IPA Series
Addressing PAD Detectors & Modules
Addressing PAD Protocol Detectors & Modules
All PAD detectors’ and modules’ addresses are set by changing the dip switches located on each device. An address must be set prior
to connection.
PAD Addresses
PAD addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.
Refer to the table below to set dip switches on any PAD detector or module.
Note: Each “gray” box indicates that the dip switch is “On,” and each “white” box indicates “Off.”
1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64
1 27 53 78 103
2 28 54 79 104
3 29 55 80 105
4 30 56 81 106
5 31 57 82 107
6 32 58 83 108
7 33 59 84 109
8 34 60 85 110
9 35 61 86 111
10 36 62 87 112
11 37 63 88 113
12 38 64 89 114
13 39 65 90 115
14 40 66 91 116
15 41 67 92 117
16 42 68 93 118
17 43 69 94 119
18 44 70 95 120
19 45 71 96 121
20 46 72 97 122
21 47 73 98 123
22 48 74 99 124
23 49 75 100 125
24 50 76 101 126
25 51 77 102 127
26 52 1 2 4 8 16 32 64 1 2 4 8 16 32 64 1 2 4 8 16 32 64
1 2 4 8 16 32 64 1 2 4 8 16 32 64
The examples shown below illustrate a PAD device’s dip switch settings: the 1st example shows a device not addressed where all dip
switch settings are in the default “Off” position, the 2nd illustrates an addressed PAD device via the dip switch settings.
All dip switches are set to the
default “OFF” position.
(Device Not Addressed)
Dip switches set for address 42.
Switches #2, 8, & 32 are “ON”.
(2+8+32=42)
Dip switches set for address 90.
Switches #2, 8, 16 & 64 are “ON”.
(2+8+16+64=90)