Specification

LD4B EU4B 4LBW 4LBM 4LBN
ENERGY DATA
Sound Rating: Class A standards
(Values at non-dimming line voltage)
Minimum Starting Temperature: -30°C (-22°F)
EMI/RFI: FCC Title 47 CFR, Part 15, Class B (Consumer)
Input Voltage: UNV (120V - 277V)
Power Factor: >0.90
(at nominal input 120-277 VAC & 100% of Rated Output Power)
Input Frequency: 50/60Hz
1000 Lumen D010 1500 Lumen D010
Input Power: 11W THD: <14% Input Power: 15.5W THD: <13%
120V Input Current: 0.09A 277V Input Current: 0.04A 120V Input Current: 0.13A 277V Input Current: 0.06A
2000 Lumen D010 3000 Lumen D010
Input Power: 21.2W THD: <9% Input Power: 27.6W THD: <10%
120V Input Current: 0.18A 277V Input Current: 0.08A 120V Input Current: 0.23A 277V Input Current: 0.10A
4000 Lumen D010
Input Power: 41.6W THD: <13%
120V Input Current: 0.35A 277V Input Current: 0.15A
120V 277V
Lumens Inrush (A) Duration (ms) Inrush (A) Duration (ms)
1000 Lumen D010 1.02 0.041 2.18 0.021
1500 Lumen D010 1.02 0.042 2.24 0.064
2000 Lumen D010 1.02 0.077 2.43 0.027
3000 Lumen D010 1.15 0.067 3.26 0.027
4000 Lumen D010 1.2 0.088 3.9 0.03
ENERGY
SAMPLE NUMBER: LD4B15D010IEMBOD
Housing Lumens
1
Voltage Driver Options
LD4B=LED Downlight 4”
Nominal Aperture
LD4BCP=LED Downlight 4”
Nominal Aperture,
Chicago Plenum
10=1000 lumens
15=1500 lumens
20=2000 lumens
30=3000 lumens
40=4000 lumens
50=5000 lumens
15
60=6000 lumens
15
Blank=120-277V
3=347V (step down
transformer)
1000-4000
D010=0-10V Dimming, 1% to 100%, 120V-277V
D010TR=0-10V or Line Voltage Dimming, 5% to 100%, 120V-277V
DE010=0-10V Dimming, 0% to 100%, 120V-277V
D5LT=Fifth Light® (DALI) Dimming, 0% to 100%, 120V-277V
DMX=DMX/RDM Dimming, 0% to 100%, 120V-277V
13
DL2=Lutron® Hi-Lume Forward Phase Dimming, 1% to 100%, 120V
Only
DL3=Lutron® Hi-Lume 3 Wire Dimming, 1% to 100%, 120V-277V
DLE=Lutron Ecosystem dimming 1% to 100%, 120V-277V
DLV=Low voltage dimming driver (1-100%) for use with DLVP system
(3000 lumen and below)
3,14
5000-6000
D010TE=0-10V 1% or trailing edge 10%, 120-277V (120V only with
trailing edge dimming)
Tunable white 1000-2000 Lumens
16
1DE010W2N2050=0-10V dimming, 0% to 100%, 120V, 2000K - 6500K
1DE010W2N2765=0-10V dimming, 0% to 100%, 120V, 2700K - 5000K
1D5LTW2N2050=Fifth Light (DALI), 0% to 100%, 120, 2000K - 6500K
1D5LTW2N2765=Fifth Light (DALI), 0% to 100%, 120V, 2700K - 5000K
2DE010W2N2050=0-10V dimming, 0% to 100%, 277V, 2000K - 6500K
2DE010W2N2765=0-10V dimming, 0% to 100%, 277V, 2700K - 5000K
2D5LTW2N2050=Fifth Light (DALI), 0% to 100%, 277V, 2000K - 6500K
2D5LTW2N2765=Fifth Light (DALI), 0% to 100%, 277V, 2700K - 5000K
EMBOD=Bodine® Emergency Module
with Remote Test Switch
3
EM7=7W Emergency Module with
Remote Test Switch
3,4
EM14=14W Emergency Module with
Remote Test Switch
3,4
IEMBOD=Bodine® Emergency Module
with Integral Test Switch
3
IEM7=7W Emergency Module with
Integral Test Switch
3,4
IEM14=14W Emergency Module with
Integral Test Switch
3,4
EMV7=7W Low Voltage Emergency
Module with Remote Test Switch
3,4
EMV14=14W Low Voltage Emergency
Module with Remote Test Switch
3,4
IEMV7=7W Low Voltage Emergency
Module with Integral Test Switch
3,4
IEMV14=14W Low Voltage Emergency
Module with Integral Test Switch
3,4
SWPD1=Factory installed WaveLinx
tilemount daylight sensor
(includes control module, sensor,
cable, and tile mount)
3,14
LWTPD1=Factory installed LumaWatt
Pro wireless sensor kit
3,14
SAMPLE NUMBER: EU4B10208035
Power Module
Lumen Levels
1
CRI Color
EU4B=4” Universal LED
Module
1020=1000, 1500, 2000 lumens
3040=3000-4000 lumens
5000=5000 lumens
15
6000=6000 lumens
15
1015IC=1000, 1500 lumen
IC rated
80=80 CRI Minimum
90=90 CRI Minimum
97=97 CRI Minimum
80 CRI
27=2700K
30=3000K
35=3500K
40=4000K
50=5000K
90 CRI
24=2400K
27=2700K
30=3000K
35=3500K
40=4000K
50=5000K
97 CRI
27=2700K
30=3000K
Dim 2 Warm
109030D2W=1000 lumen, 90 CRI, Dim 2 Warm, IC rated
159030D2W=1500 lumen, 90 CRI, Dim 2 Warm, IC rated
209030D2W=2000 lumen, 90 CRI, Dim 2 Warm
309030D2W=3000 lumen, 90 CRI, Dim 2 Warm
Tunable white
16
1020W2N902050 =1000, 1500, 2000 lumens, 90 CRI, tunable white 2000K-5000K
1020W2N902765 =1000, 1500, 2000 lumens, 90 CRI, tunable white 2700K-6500K
SAMPLE NUMBER: 4LBM1LIE
Trim Distribution
5
Flange Finish Options
4LB=4” LED N=Narrow (30° Beam), Spun Aluminum
M=Medium (50° Beam), Spun Aluminum
W=Wide (75° Beam), Spun Aluminum
S=Shallow (75° Beam), Spun Aluminum
PS=Non-conductive Shallow (75° Beam), Injection Molded white
11
CS=Cast Shallow (75° Beam), Die Cast Aluminum
BA=Baffle, Spun Aluminum
7
0=White Polymer Trim Ring
1=Self-flanged
12
2=White Painted Self-flanged
LI=Specular Clear
10
H=Semi-Specular Clear
10
WMH=Warm Haze
10
WH=Wheat
10
GPH=Graphite Haze
10
B=Specular Black
10
MW=Matte White
MB=Matte Black
9
MMS=Matte Metallic Silver
8
E=Integral Emergency Test
Switch Hole
6
Accessories
HSA4=Slope Adapter for 4” Aperture Housings, Specify Slope in 5° increments
TRM4=Metal Trim Ring, Specify Color
2
TRR4=Rimless Trim Ring
2
LGSKT4IP66=IP66 Gasket Kit
PRR4=Rimless Plaster Ring for Flush Mount
2
Bar Hangers
HB26=C-channel Bar Hanger, 26” Long, Pair
HB50=C-channel Bar Hanger, 50” Long, Pair
RMB22=Wood Joist Bar Hanger, 22” Long, Pair
Transformers
H347=347 to 120V Step Down Transformer, 75VA
H347200=347 to 120V Step Down Transformer, 200VA
Connected Lighting Systems
PORLWTPD1=LumaWatt Pro wireless sensor kit (0-10V only) field installed
14
TMSWPD1=WaveLinx tilemount daylight sensor (includes control module,
sensor, cable and tile mount) field installed
14
Notes:
1 Nominal Lumens will vary depending on selected
color, driver and reflector finish.
2 Order spun trim with polymer trim ring or die cast
with rimless flange (Consult specification sheet for
color ordering information and options).
3 Not available with Chicago Plenum.
4 ULus approved only.
5 Beam angles are nominal with LI finish trims.
6 Only available with Narrow and Medium Spun
Aluminum trims.
Required for use with all IEMBOD, IEM7, and IEM14
housings.
7 Only available with Matte White and Matte
Black Finishes.
8 Only available on CS distribution.
9 Available only on BA and CS distributions.
10 Not available on PS, CS or BA distributions.
11 Matte white and self flanged only, 2000 lumen max.
12 Flange is same finish as the reflector.
13 DMX fixtures default to full on upon loss of
DMX signal.
14 Refer to system specifications for additional
information, features, and benefits.
Order either factory installed option or accessory.
Use with 0-10V driver.
15 Product is marked spacing and must be installed
with the following minimum spacing
- Center to center of adjacent luminaires: 36”
- Center of luminaire to side of building member: 18”
- Minimum overhead: ½”
16 Non-IC