7000 Series Owners Manual

12 VOLT DC
POWER
INPUT JACK
(2.1mm pin)
DRY CONTACTS
BAS
MONITORING
FIGURE 2 – Left view of ionizer
24 VOLT AC
POWER INPUT
CONNECTION
ELECTRICAL INSTALLATION INSTRUCTIONS
WARNING: Do not connect to power before the installation is complete. Always disconnect power
to the unit before handling any of the unit components.
The 7000 Series is compatible with a variety of
primary voltage options. All models accept 24V AC
or 12V DC.
1. Connect power to ionizer using appropriate
voltage per the following:
7XX1=24V AC
7XX2=120V AC (wall pack)
7XX3=100-240V AC (power supply)
7XX4=241-277V AC (power supply)
NOTE: 24V AC power may be connected directly
to the terminal block on the outside of the unit.
The hot and neutral wires can be connected to
either screw terminal. (See figure 2)
NOTE: 100-240V AC or 241-277V AC
will require a factory supplied external
power supply to convert the primary power to 12V DC. The 12V DC power is connected to the ionizer via the 2.1
mm pin jack on the unit.
2. The models 7100, 7200, 7300 and 7400 draw less than 1 watt, 2 watts, 3 watts and 4 watts respectively. The
power source should not be protected by a circuit breaker exceeding 20 amps.
3. Power may be connected to the ionization unit using any of the following methods:
Connect 24V AC directly to the power input connection on the ionization unit where indicated.
Use a factory supplied 100-240V AC or 241-277V AC to 12V DC power supply. A 12V DC 2.1mm pin connector
shall be inserted into the 12V DC jack provided on the ionization unit. Do not use an extension cord.
Use a factory supplied 120V AC to 12V DC 500mA wall pack plugged into any electrical receptacle. A 12V DC
2.1mm pin connector shall be inserted into the 12V DC jack provided on the ionization unit. Do not use an
extension cord.
4. FIELD WIRING OPTIONS:
OPTION 1
24V AC FROM FAN CONTROL CIRCUIT
OPTION 2
100 - 240V AC OR 241-277V AC FIELD WIRED THROUGH A FACTORY PROVIDED
POWER SUPPLY INSTALLED IN A
JUNCTION BOX
OPTION 3
120V AC TO 12V DC WALL PACK PLUGGED
INTO ANY ELECTRICAL RECEPTACLE
DIRECTLY CONNECT
TO 24V AC POWER
INPUT CONNECTION
CONNECT 12V DC
2.1mm PIN TO
JACK ON UNIT
24V AC
12V DC
12V DC
FIELD WIRING BY CONTRACTOR
WIRING BY PLASMA AIR
MODELS
7100
7200
7300
7400