Datasheet
TRC ELECTRONICS, INC. 1.888.612.9514 www.trcelectronics.com/meanwell
TRC ELECTRONICS, INC.
Providing exceptional customer service since 1982
DIN Rail Power Supply • Industrial • 75W
MEAN WELL NDR-75 Series
75W Single Output Industrial DIN RAIL
NDR - 7 5 s eri e s
Protection type : Shut down o/p voltage, re-power on to recover
℃
℃℃
OUTPUT
INPUT
PROTECTION
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.6
FREQUENCY RANGE
EFFICIENCY (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load
6
0ms/230VAC 12ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
47 ~ 63Hz
85.5%
1.45A/115VAC 0.9A/230VAC
29 ~ 33V
88%
20A/115VAC 35A/230VAC
<1mA / 240VAC
14 ~ 17V
Protection type : Shut down o/p voltage, re-power on to recover
UL508, TUV EN60950-1, approved;(meet EN60204-1)EAC TP TC 004
-20 ~ +70℃ (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03%/℃ (0 ~ 50℃)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2
-6
486.2K hrs min. MIL-HDBK-217F (25℃)
32*125.2*102mm (W*H*D)
0.51Kg; 28pcs/15.3Kg/1.22CUFT
NDR-75-24
24V
3.2A
0 ~ 3.2A
76.8W
120mVp-p
24 ~ 28V
±1.0%
±0.5%
±1.0%
NDR-75-12
12V
6.3A
0 ~ 6.3A
75.6W
80mVp-p
12 ~ 14V
±2.0%
±0.5%
±1.0%
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
ENVIRONMENT
SAFETY &
EMC
(Note 4)
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
EMC IMMUNITY
EMC EMISSION
105 ~ 130% rated output power
Prot
ection type : Constant current limiting, recovers automatically after fault condition is removed
56 ~ 65V
89%
NDR-75-48
48V
1.6A
0 ~ 1.6A
76.8W
150mVp-p
48 ~ 55V
±1.0%
±0.5%
±1.0%
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020
File Name:NDR-75-SPEC 2018-06-05