IP-based 4-/8-port Switched Power Manager IPM-4220/IPM-8220
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Copyright Copyright 2016 by PLANET Technology Corp. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, electronic, mechanical, magnetic, optical, chemical, manual or otherwise, without the prior written permission of PLANET.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Federal Communication Commission (FCC) Radiation Exposure Statement This equipment complies with FCC radiation exposure set forth for an uncontrolled environment.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Table of Contents Chapter 1. Product Introduction ......................................................................................... 6 1.1 Package Contents ...................................................................................................... 6 1.2 Overview .................................................................................................................... 7 1.3 Features ........................
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 4.4 4.5 4.3.4 SNMP..................................................................................................... 49 4.3.5 Syslog .................................................................................................... 50 4.3.6 Serial Port (UART) ................................................................................. 51 4.3.7 Peripheral Parameters .........................................................
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Chapter 1. Product Introduction 1.1 Package Contents The package should contain the following: 1 x Switched IPM 1 x Quick Installation Guide 1 x Power cord 1 x Quick Rack-mounting Kit Installation Guide (For IPM-8220) If any of the above items are missing, please contact your seller immediately.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 1.2 Overview Meeting All Your Power Needs via IP-based Power Outlets PLANET IPM-4220/8220 is a 4-/8-port IP Power Management (IPM) device that provides the useful function of managing power for any combination to connect with itself. With the innovative IP-based technology, PLANET has made the traditional power management equipment into true networking devices.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Scheduled Power On/Off The IP-based Switched Power Manager allows you to pre-define a power schedule for IT equipment. It alerts users to an upcoming shutdown, and then waits a predefined amount of time to allow users to finish their work and sign off.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Energy and Cost Saving You can also check the current energy consumption in your office within the configuration interface of the IPM-4220/8220. It helps you reduce energy consumption, thus saving expenses on utilities.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 1.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Security ■ Web page supports 1024-bit SSL security encryption transmission ■ Supports Secure Socket Layer V3 and Secure Shell V1 protocols ■ Administrator and multiple users with password protection for double-layer security ■ IP Filtering -- Address-specific IP security masks to prevent unauthorized access - 11 -
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 1.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Management User Account General/Manage/Administrator Management Utility Web browser, SNMP software, Windows-based utility, Telnet Security IP filter/MAC filter/Secure 128-bit SSL encryption Standards Conformance Computer Interface Regulatory Compliance IEEE 802.3 10BASE-T IEEE 802.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Chapter 2. Hardware Interface 2.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 11 12 13 14 Power Outlet Note: The maximum output current is 16 amps.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 LCD menu shows the total current. Hold the Switch/Set button for 3 seconds (until a long beep is heard) to enter alarm current setting. Press the Switch/Set button to increase the alarm current by 0.5A in each press. Hold the Switch/Set button for 3 seconds (until a “beep” is heard) to save the setting. Press the Switch/Set button until it shows the maximum current.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 IPM-8220 Rear Panel IPM-8220 Front Panel System Indicating Light 1 Slow flashing: Normal operating Rapid flashing: Normal updating 2 Reset and Warning Indicating Light 3 Temperature/Humidity Port for IPM-ESB Connection 4 Reset Button 5 RJ45 Ethernet Port 6 USB Connected Port (Future Feature) 7 COM2/1 2 Com Ports provided to enable terminal control, API control and 2 mutual cascading 8 Circuit Breaker Protection 9 Power In
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 power switch control and IP; set alarm current 14 Buzzer Alarm Indicating Light 15 Lights remaining lit: Alarm has occurred Slow flashing: There is current overloading 16 Power Outlet Indicating Light IPM-8220 Current Panel Operation When the LCD panel only displays figures and the sign of "A (AMP)", it means total current.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Press the Set button to show the voltage information. Press the Set button to show the maximum current record of all branches (branch 1 and branch 2). Hold the Set button for 3 seconds (until a long beep is heard) to adjust to a zero point. IPM-8220 Power Outlet Panel Operation When the LCD panel shows figures and "0", the information shown is the branch circuit power outlet.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 operated through the panel. Please go to the Peripheral of web UI and check the setting. IPM-8220 IP Panel Operation Press the Switch button to show words like "IP" Press the Set button to switch the display of each IP address. IP can only be set by the web page rather than the LCD panel. 2.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 2. For the main power supply control of the Switched IPM, set the UART type as daisy chain. 3. For the secondary power supply control of the Switched IPM, set the UART type as API. The power outlet of the main and secondary remote power control devices can be set to determine the power outlet requiring concatenation. 2.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Use the attachments/accessories specified by the manufacturer only. Please avoid any items or liquids entering the device because their contact with dangerous voltage points or short-circuit parts may cause a fire or electric shock. 2.4 Hardware Installation The IPM-8220 provides a standard 19-inch rack for the installation of devices.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 2.5 Initial Utility Installation PLANET “IP Search” is a software utility used to search the IP Metered PDU product on a network quickly and with ease. Step 1: Please download the IP Search tool from PLANET Download Center. Step 2: Please press the “Refresh” button to find out your IP Metered PDU. 1. Before searching the IP, please make sure your PC is in the same IP segment as control gateway. 2.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Chapter 3. Quick Setup In this section users can learn how to query device IP and how to set language, account password, network and time zone through daemon. 3.1 Network Connection After the device is connected to the network, IP can be acquired automatically through DHCP server (The device IP will be preset to 192.168.0.10 if there is no DHCP server.).
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Step 3: Host Setting The product is assigned dynamically (DHCP). To specify a fixed IP address, please fill in IP Address, Subnet Mask and Gateway. Press Next to continue. Step 4: DNS Setting Key in the DNS server, provided by ISP providers, and then you can set up two DNS servers. Press Next to continue. Step 5: Web Server Https can help protect streaming data transmission over the internal on the higher security level.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Step 6: Time Format Select the time format to show in the system. Press Next to continue. Step 7: Time Server Setting User can set up device time synchronized with Time Server. Press Next to continue. Step 8: Time zone Please fill in the time zone where the device is. The system is based on Greenwich Mean Time, and thus, an accuracy setting to time zone may affect the time record of events and chart. Press Next to continue.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 - 27 -
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Chapter 4. Web-based Management This section provides instructions about how to use the web interface to configure and control the IP Power Manager remotely. 4.1 Monitor After a successful login, the web page will display the following operation menu where each part is illustrated below: 4.1.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Name Description Description of each power infeed. Each light signal has three states: "Normal", "Alert" and "No Access". Monitor Normal: “Offline Monitor” is checked. And external temperature is not higher than “High Alarm” or lower than “Low Alarm” setting. Monitor Alert: “Offline Monitor” is checked. And external temperature is higher than “High Alarm” or lower than “Low Alarm” setting.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Name: Description of each power infeed. Overload Current: Input the current value of the overload power; alarms will be given when the input power current exceeds this alarm value. High Alarm: Set up the values of high infeed alarm. When current is higher than you set, the alarm will occur. Low Alarm: Set up the values of low infeed alarm. When current is lower than you set, the alarm will occur.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description registered on the computer and the computer state will show the sign of giving normal registration. There are two computer states for power outlet: "Normal online state", and "Abnormal online state". : Normal online state : Abnormal online state Move the mouse over the sign for its detailed information, and the menu is displayed as follows: Displays the current power outlet on-off state.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Delete Group: Delete the group user that is not necessary. Add Group: Click on Add Group to create a group. After clicking it, Add Group window will pop up. Enter group name and mark the ports you expect to manage, and press Add to build the group, continuously adding is permitted here. Press Cancel to return to main tab. 4.1.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Normal: “Offline Monitor” is checked. And external temperature is not higher than “High Alarm” or lower than “Low Alarm” setting. Alert: “Offline Monitor” is checked. And external temperature is higher than “High Alarm” or lower than “Low Alarm” setting. No Access: Means user does not have any authority to operate the infeed.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Displays the current power outlet on-off state. For operation of power Switch outlet on/off, click the on/off icon with the mouse for commands of "On", “Off”, and “Reboot”. To be displayed after concatenation is enabled is the power outlet of Sync Port this line that will be linked with the outlet displayed in the Sync Port of concatenated device.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters 4.1.4 Description Temperature Display the information of Offline Monitor, Status and Temperature Value of the sensor. Parameters Name Offline Monitor Description Description of temp port. Check to enable to monitor the state of temp sensor. When abnormal temp occurs, device will send alert via the specified email.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description than “Low Alarm” setting. Non-Monitor Alert: “Offline Monitor” is not checked. And external temperature is higher than “High Alarm” or lower than “Low Alarm” setting. Non-Monitor Off-line: “Offline Monitor” is not checked. Temperature Probe is not connected to device now.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Sensor state: Device Temp has 2 states: "Monitor Normal", and "Monitor Alert". Monitor Normal: “Offline Monitor” is checked. And external temperature is not higher than “High Alarm” or lower than “Low Alarm” setting. Monitor Alert: “Offline Monitor” is checked. And external temperature is higher than “High Alarm” or lower than “Low Alarm” setting.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Monitor Off-line: “Offline Monitor” is checked. Humidity Probe is not connected to PDU now. Non-Monitor Normal: “Offline Monitor” is not checked. And external humidity is not higher than “High Alarm” or lower than “Low Alarm” setting. Non-Monitor Alert: “Offline Monitor” is not checked. And external humidity is higher than “High Alarm” or lower than “Low Alarm” setting.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Model Outlet Total Description The device of daisy chain. The outlet power port. Device of daisy chain has 2 states: "Monitor Normal", "Monitor Alert". Normal online state. Abnormal online state Status Move the mouse over the icons for its detailed information, and the menu is displayed as follows: 4.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Name Power on delay Power off delay Description Description of each power outlet. Set the number of seconds that device waits after a command is issued before applying power to an outlet. Set the number of seconds that device waits after a command is issued before removing power from an outlet.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 4.2.3 Schedule In this option, work schedule of the time for power outlet on/off is seen. Parameters Description Set the work cycle of the power outlet; the cycle can be divided into Period Holiday, Month, Week, and Day. For example, if the cycle is Day, it means the power will perform the command at the set time every day. Time Action Delete 4.2.4 Set the work hours of the power outlet in the drop-down list.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Re-Ping time (Min.) 4.2.5 Description The delay time for re-executing PING detection when the network device is on after network device reboots. Monitor (Only for IPM-8220) This function provides the ability to set power outlet current value, real-time off of power outlet in case of any current abnormality to avoid any damage to the devices connected with the outlet. Parameters Overload 4.2.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Type: Use drop-down list to select peripheral type. (e.g., External Temp) Port: Select the port to be monitored. Term: You may choose the symbols: > (higher), < (lower) and = (equal). Monitor condition Value: The device would command the order as temp reaches this value. Duration: The duration of value that is compliant with the peripheral conditions.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Press "Save" after selecting a single power outlet or selecting all to copy the selected outlet parameters to the clicked power outlet(s). 4.3 System On this web page, users can set Network, Email server, Message server, SNMP, SysLog, Peripheral parameters, and other relevant data. 4.3.1 Network Setting This menu is mainly for setting the basic data of network.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Primary DNS Server Secondary DNS Server Description Configure the IP and DNS server addresses for Network Adapter 1. Configure the IP and DNS server addresses for Network Adapter 2. Parameters Description Enabled Http Allows browser to connect with smart monitor by HTTP. Enabled Https Allows browser to connect with smart monitor by HTTP SSL. Http Port Provides browser to communicate by HTTP with smart monitor.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description When Disable ICMP Response check box is selected, the Disable ICMP examination will not be responded. Response 4.3.2 Email Server When there is a triggered warning from the setup of this PDU, this device will send out alert message to the preset email accounts.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Password Email Test 4.3.3 Description The password to log in to mail server. After setting up the above info, you can send a test mail to make sure this function is normal. SMS Server In this section, user can set up the warning message and info to the SMS server. The protocol here is supported by many SMS suppliers’ (ISP) API.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters SMS Test Description After setting up the above info, you can send a test mail to make sure this function is normal. Parameters @@DEVICENAME@@ @@ACCOUNT@@ @@PASSWORD@@ @@GSMNUM@@ @@MSG@@ @@IP@@ Description The device name will show when sending a message. The account to send the message. The password to send the message. The number to send the message. Message content will show when sending a message.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 4.3.4 SNMP You can set up SNMP Agent and SNMP Trap on this page. Parameters SNMP v1/v2 Enable SNMP Port Read Community SNMP Writing Write Community Description Enable SNMP v1/v2. Set the destination port. Default is 161. Key-in passwords in the Community Name field. Default is public. Select the checkbox to enable SNMP Write-in. Key-in passwords in the Community Name field. Default is private.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description Private Password For private password, use DES. Select DES type to key-in password. Parameters Description sysName The name displayed on SNMPAgent. sysContact The contact displayed on SNMPAgent. sysLocation The location displayed on SNMPAgent. Parameters Host SNMP Trap Port Authentication String SNMP Test 4.3.5 Description The Host IP address of SNMP Trap. The phase connects to SNMP Trap.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Host Enter Syslog Server Host IP. Port Enter Connect Port for Syslog Server. Default is 514. Syslog Test 4.3.6 Description After setting up the above info, test it to make sure this function is normal. Serial Port (UART) This menu is mainly for setting the data of COM 1 (UART 1), and COM 2 (UART 2).
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description operate the device through terminal program API: Other devices can operate the current device through API protocol. As for the use of API, please refer to the appendix UART API protocol. UPS: Enable this when the device is to be connected with UPS to monitor UPS information. When the type selected is UPS, the following window will be displayed; press "search" to search the device after selecting the "type".
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Released Load (Range) Temp Scale Released Temp. (Range) Description You may set up threshold current to avoid floating power triggered warning reaction. The warning will be dismissed by system when power current is lower than threshold current. You can choose either Celsius or Fahrenheit. You may set up threshold temp. to avoid floating power triggered warning reaction. The warning will be dismissed by system when temp.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters High Temp Suggested High Temp Suggested Low Temp Low Temp Description Display the RCI type maximum load capacity for the temperature. Display the RCI type high capacity for the temperature. Display the RCI type low capacity for the temperature. Display the RCI type minimum load capacity for the temperature.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Direction (only for IPM-8220) Locked or not "SET Button" Timeout Locked Time Timeout 4.3.8 Description You may set up threshold current to avoid floating power triggered warning reaction. The warning will be dismissed by system when power current is lower than threshold current. User cannot control the switch through LED panel as it is locked.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Description MQTT Host Enter MQTT Host IP. MQTT Port Enter Connect Port for MQTT. Default is 1883. Parameters IP Lock-up Period (Min.) IP Login Times Description The period of such IP has been locked up. The number of times that user logs in. 4.4 Firewall In this tab, you may set up permitted IP or Mac address to access this remote power manager. 4.4.1 IP Filter User can set up permitted IP section on this page.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Enable IP Filter Allowed IP Section 4.4.2 Description Allow authorized IP address to access this device. After keying in permitted IP section, please click ADD to implement this action. To delete a specific IP address, please click “X”. MAC filter This menu is mainly for setting of Network MAC Address having access to this device.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Modify Description Modify the previous setting. Operation of Alarm. Click Delete icon: browser will pop up a Confirmation of delete Delete window. Click Confirm: this Account cannot be utilized any longer. 4.5.1 Basic Info To set up account, password and user type. Parameters Account Password Description The account to log in to this device. The password to log in to this device.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 4.5.2 Outlet Authority Outlet Authority tab is mainly to open up outlet authority to other users. 4.5.3 Email System would send email when alarm occurs. Parameters Enable Alert ‘Send’ To Description Check to open email alarm system informed by email. Enter the mail address of Receiver.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Parameter Description Use the checkbox to enable the setting. The system will follow the warning method you choose. Use the checkbox to enable the setting. When abnormal condition of Infeed infeed happens, system will send a warning message by the way you command. Outlet Control Outlet Check to enable warning as abnormal condition of switch operation occurs. Check to enable warning as abnormal condition of outlet occurs.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Cellphone Parameter Description Informed by short message, please fill out the right cellphone number. Use the checkbox to enable the setting. The system will follow the warning method you choose. Use the checkbox to enable the setting. When abnormal condition of Infeed infeed happens, system will send a warning message by the way you command.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 4.6 Time You can set up the time server on this page. Parameters Device Time Time Synchronization Synchronization with Time Server Description Date and time of the system. You may either scroll down to select Sync with computer or Manual Setting. Select this time method if you want the system time of this power switch to be the same as Greenwich Mean Time (GMT).
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Enable daylight saving time Description Set the Daylight saving time from Sunday to Saturday 4.7 Chart This menu is mainly for query infeed, device temperature and statistic data. Parameters Description Category You may either scroll down to select infeed or device temperature. Time Interval You may either scroll down to select 1 min. or 30 mins. Search See the reference date chart as shown in the table.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 4.8 Event The web page recorded the recent 200 logs, including the time, type and message. Parameters Refresh Download Delete Description Click the Refresh button to refresh the screen. Click the Download button to save the event log information. The event log is saved in .txt format. Click the Delete button to delete the Event logs. 4.9 Upgrade This web page is for upgrading the device firmware and the configuration files.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Parameters Upload firmware Upload configuration Download configuration Description To update the firmware online, click “Browse…” to select the firmware. Then click “Upgrade” to proceed. Upgrade from previous saved setting. Download the current setting to PC.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Chapter 5. Console Operation In this chapter, users can learn how to operate power On/off and set the network parameters through Console. When learning console operation, users should firstly set the type of device UART1 as Console and set relevant parameters. As for the setting of UART1, please refer to 4.3.6 Serial Port (UART). 5.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 After setting is done, the HyperTerminal will display the sign-in menu; please enter the system account and password (admin and admin) established in device daemon. After entering finished, operation menu will be displayed to control power switch and set network data. Operation method of the menu is as follows: 1. Press ↑ or ^W can drift the menu, >> drift upward. 2. Press ↓ or ^Z can drift the menu, >> drift downward. 3.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 5.2 Power Control After selecting "OUTLET" from the main menu, press → or ^D to enter power control operation. Move Up and Down keys to move the cursor to the power outlet to be operated. When the Outlet is ON, press Tab for deciding the state of this line: Reboot or Off. After selection, press "Enter" or "E" to enter the Query window to decide any operation of this outlet; if yes, press "Y"; otherwise "No".
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 5.3 System Preferences After selecting "SYS" from the main menu, press → or ^D to enter System Preferences setting. 5.3.1 Network Preferences After selecting "NetWork" from the main menu, press → or ^D to enter System Preferences setting. 5.3.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 setting is modifying the system administrator password. 5.4 Firewall Preference After selecting "Firewall" from the main menu, press → or ^D to enter System Preferences setting.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 5.5 RELOAD Preference After selecting "RELOAD" from the main menu, press → or ^D to enter the query windows to reload all data; if yes, press "Y", then the device will reload network, user and firewall data, and the data revised on the terminal before canceling.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 5.6 Parameter Saving After selecting "SAVE" from the main menu, press → or ^D to enter the query windows to save and reboot the device; if yes, press "Y", then the device will save the revised data and reboot.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 5.7 Logout After selecting "LOGOUT" from the main menu, press → or ^D to enter the query windows; if press "Y" , then the terminal program will be logged out and the sign-in menu will be displayed.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Appendix A: Resetting to Default via Reset Button Users who forget the network account and password of the product can press "Reset" to recover to the factory default values, and the device will reboot at the same time. Step 1. Press and hold "RESET" for more than 3 seconds. When LED starts flashing, release the hold. You are then asked fill out the admin account and password as admin (add a new account if no admin account).
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Appendix B: HTTP Message API Example A Message API example of a message service provider is given below. The transmission mode is Get in TTP protocol, and the URL format is as follows: http://SMLWsip/httpSMLWs.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Press the icon on the right side of the screen to see message format as a reference. Parameters @@DEVICENAME@@ @@ACCOUNT@@ @@PASSWORD@@ @@GSMNUM@@ @@MSG@@ @@IP@@ Description The device name will show when sending a message. The account will send the message. The password will send the message. The number will send the message. Message content will show when sending a message. Device IP will show when sending a message.
IP-based 4/8-port Switched Power Manager Power IPM-4220 / IPM-8220 Message format Description Required Company code (depid=xxxxxx) & User's Account Required (account=@@ACCOUNT@@)& User's password Required (password=@@PASSWORD@@)& Cellphone number Required (dstaddr=@@GSMLWNUM@@)& Device IP & Message content (IPMbody=@@IP@@,@@MSG@@) - 77 - This format is changeable with the content.