2. Tighten the wire-clamp screws for preventing the wires from loosening.
1 2 3 4 5 6
Power 1 Fault Power 2
- + - +
The wire gauge for the terminal block should be in the range between 12 and 24 AWG.
2.1.5 Wiring the Fault Alarm Contact
The fault alarm contacts are in the middle of the terminal block connector as the picture shows below. Inserting the wires, the
Industrial Managed Switch will detect the fault status of the power failure, or port link failure and then forms an open circuit. The
following illustration shows an application example for wiring the fault alarm contacts.
1 2 3 4 5 6
Insert the wires into the fault alarm contacts
1. The wire gauge for the terminal block should be in the range between 12 and 24 AWG.
2. Alarm relay circuit accepts up to 30V, max. 3A currents.