Figure 4-6-1-7: PD Alive Check Configuration Screenshot
The page includes the following fields:
Object Description
Mode
Allows user to enable or disable per port PD Alive Check function. As default value
all ports are disabled.
Ping PD IP Address
This coulumn allows user to set PoE device IP address here for system making ping
to the PoE device. Please be noticed that the PDs IP address must be set to the
same network segment with IGS-5225-4UP1T2S/8P4S/8P4S-12V/8P2S/8P2S2X
PoE Switch.
Interval Time (10~300s)
This column allows user to set how long system should be issue a ping request to
PD for detecting PD is alive or dead. Interval time range is from 10 seconds to 300
seconds.
Retry Count (1~5)
This column allows user to set how many times system rerry ping to PD. For
example, if we set count 2, the meaning is that if system retry ping to the PD and the
PD doesnt response continuously, the PoE port will be reset.
Action
Allows user to set which action will be apply if the PD witout any response.
IGS-5225-4UP1T2S/8P4S/8P4S-12V/8P2S/8P2S2X PoE Switch offers 3 actions as
following.
PD Reboot: It menas system will reset the PoE port that connected the PD.
Reboot & Alarm: It means system will reset the PoE port and issue an alarm
message via Syslog, SMTP.
Alarm: It means system will issue an alarm message via Syslog, SMTP.
Reboot Time (30~180s)
This column allows user to set the PoE PD device rebooting time, due to there are
so many kind of PoE PD device on the market and theyhave different rebooting