User's Manual
9
2. Tighten the wire-clamp screws for preventing the wires from loosening.
1 2 3 4 5 6
Power 1 Fault Power 2
+ - + -
Note
1. The wire gauge for the terminal block should be in the range
between 12 and 24 AWG.
2. The DC power input range is 48V ~ 56V DC.
Grounding the Device
Users MUST complete grounding wired with the device; otherwise, a sudden
lightning could cause fatal damage to the device.
PWR1
PWR2
Fault
DC Input:
48-56V , 5.5A max.
Max. fault loading: 24V, 1A
1 2 3 4 5 6
Earth Ground
2.6 Wiring the Fault Alarm Contact
The fault alarm contacts are in the middle of the terminal block connector as the
picture shows below. Inserting the wires, the Industrial PoE+ Switch will detect