Lightning Protection Grounding
The lightning protection system is an independent system consisting of a lightning
rod, conductor and connection joint with the grounding system. The grounding
system usually is shared with the power reference grounding, and green and
yellow ground cable grounding. Lightning protection grounding is a building
requirement,notaspecicrequirementoftheChassisSwitch.
Electromagnetic Compliance Grounding
This refers to the grounding in compliance with CS-6306R electromagnetic
compatibility requirements, including shielded grounding, lter grounds, noise, and
interference control and level reference. The overall grounding requirements are
the sum total of the above. Ground resistance value should be less than 1 ohm.
The CS-6306R provides chassis grounding post in the lower front chassis, marked
as “GND”. Chassis protection grounding should be properly connected to the rack
grounding connector.
The ground cabling procedures are listed below:
Step 1 Remove the nuts from the front chassis grounding posts.
Step 2 Wrap one end of the green and yellow grounding cable to the grounding
posts.
Step 3 Attachthegroundingpostnutandtightenwell.
Step 4 Attach the other end of the grounding cable to the rack grounding
connector.
The grounding cable should be made of a good conductor, and the
diameter should be determined by the possible maximum current
that may pass through. Bare conductor cabling is forbidden.
Ground resistance value: The combined grounding resistance
should be less than 1 ohm.