B.1 Recommended Use of the Connected Wires
(Applicable to the system with voltage attenuation less than 3%) The following table is applicable to the
applications in the system.
Distance in feet ( meters )
Amps 24 AWG 22 AWG 20 AWG 18 AWG 16 AWG 14 AWG
2.5
5.6 ft (1.95m) 8.8 ft (2.70m) 14.12 ft (4.30m) 22.50 ft (6.86m) 36.0 ft (11.0m) 56.4 ft (17.22m)
5.0
2.80 ft (0.86m) 4.4 ft (1.36m) 7.06 ft (2.16m) 11.26 ft (3.42m) 18.0 ft (5.48m) 28.2 ft (8.6m)
7.5
1.86 ft (0.56m) 2.96 ft (0.90m) 4.70 ft (1.44m) 7.50 ft (2.28m) 12.0 ft (3.66m) 18.82 ft (5.74m)
10
1.40 ft (0.42m) 2.22ft (0.68m) 3.52 ft (1.08m) 5.62 ft (1.72m) 9.0 ft (2.74m) 14.12 ft (4.30m)
12.5
1.12 ft (0.34m) 1.78ft (0.54m) 2.82 ft (0.86m) 4.50 ft (1.38m) 7.20 ft (2.20m) 11.30 ft (3.44m)
15
0.94 ft (0.28m) 1.48 ft (0.46m) 2.36 ft (0.72m) 3.76 ft (1.14m) 6.0 ft (1.82m) 9.42 ft (2.86m)
B.2 Recommended Settings for Different Batteries
We suggest Nickel-cadmium battery and Lead-acid battery for BSP-360. You could set the Battery type at
Battery Management on the web.
Description Specifications
Battery type Nickel-cadmium Battery
System voltage
24V
Maximum input voltage 45V DC
Output voltage for load Equal to battery’s voltage
Float charge voltage 27.2V DC (26.0~30.0V)
Absorption charge voltage 29.2V DC (28.0~32.0V)