4.5 Battery Management
The page provides for the user to configure the battery parameters so as to achieve the best application
condition as the screen in Figure 4-5-1 appears. Table 4-5-1 describes the Battery Management Objects
Screen of Renewable Energy Switch. Before the configuration operation, please contact the suppliers of your
battery for the product‐specific parameters.
Figure 4-5-1 Battery Management Web Page Screen
Object Description
Battery Type
Nickel-cadmium or Lead-acid battery.
Battery Capacity
Enter the Battery Capacity to the item.
Please ask the battery vendor about this information.
Install Time of Battery
Enter the install time of battery to the item.
Battery Life
Enter the battery life to the item.
Please ask the battery vendor about this information.
Float Charge Voltage
DC 27.2V ( 26.0~30.0V)
When the battery charge completes the charging process, its voltage will
drop to a float charge voltage and maintain at this voltage with a minimal
charging current for supplemental battery charging.
Absorption Charge Voltage
DC 29.2V (28.0~32.0V)
When the battery voltage achieves the value of absorption charge
voltage, the controller will maintain this voltage and charge for a period of
time which will not cause excessive charging of the battery.
Low Voltage Disconnection DC 22.2V (21.0~25.0V)