Datasheet
7
49
Technical data
Control and signalling devices   line
Main features
 High reliability contact blocks with quadruple 
contact points self-cleaning contacts
 Gold plated contacts version
 Positive opening NC contacts according to 
IEC 6097-5-1
General data
Protection degree:  IP20 on the terminals according to IEC 60529
Ambient temperature:  -40°C +80°C
Mechanical endurance:  20 million operations cycles 
Max operating frequency:  3600 operations cycles/hour
Utilization requirements:  see page 78
Contact block
Contacts commutation force:  2NO: 1,7 N
  2NC: 2 N
  1NO+1NC: 2,7 N (NO), 2,2 N (NC)
Actuating force at end travel:  2NO: 3,8 N, 
  2NC: 3,8 N
  1NO+1NC: 4,5 N 
Positive opening force:  17 N
Activating speed:  min 1 mm/s 
  max 0,5 m/s
Contacts material:  silver contacts (standard)
  Contacts for weak current in silver, 
  1µm thick gold-plating (on request)
Contacts form:  “V shape” self-cleaning contacts with 
  quadruple contact points
Conductors cross section:  min 1 x 0,34 mm
2 
(1 x AWG 22)
  max 2 x 1,5 mm
2 
(2 x AWG 16)
Screw terminal driving torque:  0,6 ... 0,8 Nm
Electrical data Utilization categories
Alternate current: AC15 (50÷60 Hz)
Ue (V)  24  48  120  250
Ie (A)  6  6  6  6
Direct current: DC13
Ue (V)  24  48  125  250
Ie (A)  2,5  1,3  0,6  0,3
Thermal current (Ith):  10 A
Rated insulation voltage (Ui):  250 Vac/dc
Protection against short circuits:  fuse 10 A 500 V type gG/gL
Rated impulse withstand voltage (U
imp
):  4 kV
Pollution degree:  3
Markings and quality marks:
Approval GOST: POCC IT.AB24.B04512
General characteristics
Positive opening
All NC contacts are suitable for safety applications.
NC contacts have positive opening according to IEC 60947-5-1.
High reliability self-cleaning contacts
“V shape” self-cleaning contacts with quadruple contact points.
This  shape,  thanks  to  its  quadruple  support,  allows  to  reduce  the 
probability  of  contact  wrong  switching.  Furthermore  it  highly 
improves 
the  contacts  reliability  in 
case of dust.
Double contact blocks
 Installation for safety applications:
Use  only  switches  marked  with  the  symbol  . The  safety  circuit  must  always  be 
connected  with  the  NC  contacts  (normally  closed  contacts:  1-2)  as  stated  in  the 
standard EN 60947-5-1, encl. K, par. 2. 
In conformity with standards:
IEC 60947-1, IEC 60947-5-1, IEC 60204-1, EN 60947-1, EN 60947-5-1, EN 60204-1, 
UL 508, CSA 22-2 N°14.
In conformity with requirements requested by:
Low Voltage Directive 2006/95/EC, Machinery Directive 2006/42/EC and 
Electromagnetic Compatibility 2004/108/EC.
Positive contact opening in conformity with standards:
IEC 60947-5-1, EN 60947-5-1, VDE 0660-206.
Modularity and compact dimensions
The  EROUND  double 
contact  blocks  are 
distinguished  by  their 
more compact dimensions 
as  compared to  the  other 
double  contact  blocks 
found on the market.
Thanks  to  their  compact 
dimensions, these versions 
can also be  mounted on 
the bottom of boxes.
However,  these  double 
contact  blocks  have  the 
same  vertical  overall 
dimensions  of  the 
EROUND  single  contact 
blocks: this  ensures  that 
single  and  double  contact 
blocks  can  be  piled  up 
together on several levels, 
and can  be interchanged 
during  the  installation 
stage.