Troubleshooting Guide

Table Of Contents
For All 2016 and newer Models: Wall Mount, Concealed Duct / Cassette / Floor Console / Floor
Ceiling):
1) Wall Mounted:
WS009GMF
I22HLD, WS012GMFI22HLD, WS018GMFI22HLD, WS024GMFI22HLD.
2)
C
eiling Concealed:
RB009GMFI
LDFHD, RB012GMFILDFHD, RB018GMFILDFHD, RB024GMFILDFHD.
3) Cassette:
CB009GMFI
LDFHD, CB012GMFILDFHD, CB018GMFILDFHD, CB024GMFILDFHD.
4) Floor Console:
FB009GMFI
LDFHD, FB012GMFILDFHD.
5) Floor / Ceiling:
UB018GMFI
LDFHD, UB024GMFILDFHD.
Operation lamp
Timer
lamp
Display LED STATUS
ODU
Error
1 time
X E0 Indoor unit EEPROM parameter error
——
2 times
X E1 Communication malfunction between indoor and outdoor units
E2
4 times
X E3 Indoor fan speed malfunction
——
5 times
X E4 Indoor room temperature sensor (T1 ) malfunction
——
6 times
X E5
Evaporator coil temperature sensor (T2) malfunction
——
8 times
X EE Water-level alarm malfunction
1 times
F0 Current overload protection
——
2 times
F1 Outdoor ambient temperature sensor (T4 ) malfunction
E4
3 times
F2 Condenser coil temperature sensor (T3) malfunction
E4
4 times
F3 Compressor discharge temperature sensor (T5) malfunction
E4
5 times
F4 Outdoor unit EEPROM parameter error
E0
6 times
F5 Outdoor fan speed malfunction
E8
7 times
F6
Indoor coil outlet pipe sensor(Located on outdoor unit low pressure
valve)
——
8 times
F7
Communication malfunction between Cassette optional lift panel
and the unit.
——
9 times
F8 Cassette optional lift panel malfunction
——
10 times
F9 Cassette optional lift panel not closed
——
1 times
P0 Inverter module (IPM) malfunction
P6
2 times
P1 Over-voltage or under-voltage protection
E5
3 times
P2 High temperature protection of IPM board
——
4 times
P3 Low ambient temperature protection
LP
5 times
P4 Compressor drive malfunction
——
6 times
P5
(——)
Indoor units mode conflict
——
7 times
P6 Low pressure protection
P2
flash , light, X extinguished