MULTI-SPLIT SYSTEM AIR CONDITIONER / HEAT PUMP YN-M Series Inverter++ Models Two, Three, Four, and Five Zones (Dual, Triple, Quad, and Quint Multi) Installation Manual IMPORTANT NOTE: • Read this manual carefully before installing or operating your new air conditioning unit. Be sure to store this manual for your future reference. • This manual only describes the outdoor unit of the system. For more info on the indoor unit, refer to its installation manual.
Table of Contents Installation Manual 1 Accessories.......................................................................04 2 Safety Precautions ................................................... 05 3 Installation Overview............................................ 06 4 Installation Diagram...............................................07 5 Specifications.................................................................08 6 Outdoor Unit Installation....................................09 a.
7 Refrigerant Piping Connection.....................12 L1 L2 8 Wiring...................................................................14 a. Outdoor Unit Wiring.............................14 b. Wiring Figure..............................................16 9 Air Evacuation...........................................................19 MC MC a. Evacuation Instructions....................................19 b. Note on Adding Refrigerant.........................26 10 Test Run.............................
1 Accessories The air conditioning system comes with the below accessories. Use all of the installation parts and accessories to install the air conditioner. Improper or incomplete installation can result in water leakage, electrical shock and fire, or equipment failure. Name Shape Quantity Drain joint (some models) 1 Seal ring (some models) 1 Connecting pipe assembly Liquid side Gas side Ø6.35 (1/4) Ø9.52 (3/8) Ø9.52 (3/8) Ø12.7 (1/2) Ø15.
Safety Precautions 2 Read and Understand All Safety Precautions Before Installation Incorrect installation due to negligence of instructions can lead to serious damage or injury. The magnitude of potential damages or injuries is classified as either a WARNING or CAUTION. Failure to observe a warning may result in severe injury or death. The appliance must be installed in full accordance with all relevant national regulations. WARNING Failure to observe a caution may result in injury or equipment damage.
Unit Installation Overview 3 Installation Overview INSTALLATION ORDER 1 2 3 L1 Install the outdoor unit (Page 9) Connect the refrigerant pipes (Page 12) 5 Connect the wires (Page 14) 4 MC Perform a test run (Page 22) Page 6 L2 MC Evacuate each of the line sets and Indoor Units.
24” Installation Diagram 12” 4” 24” ” 80 Dual (2) Zone Triple (3) Zone If wall mount condenser bracket is used, rear clerance can be reduced to 6” Quad (4) Zone Quint (5) Zone Fig. 4.1 Safety Precautions CAUTION CAUTION This illustration is for demonstration purposes only. The actual shape of your air conditioner may be slightly different. • Copper lines must be independently and individually insulated. • To prevent wall damage, use a stud finder to locate studs. • A minimum pipe run of 3 m.
5 Specifications Power source voltage Connected units 1 to 5 units Stop time 3 min or more voltage fluctuation within ±10% of rated voltage voltage drop during start within ±15% of rated voltage interval phase unbalance within ± 3% of rated voltage Table 5.2 2 Zone 3 Zone Unit: m/ft. 4 Zone 5 Zone Max. length for all rooms 40/130 60/200 80/260 80/260 Max. length for one indoor unit 25/80 30/100 35/115 35/115 Max.
6 Outdoor Unit Installation Outdoor Unit Installation Instructions √ √ √ √ √ The area must be free of combustible gases and chemicals. The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length. If possible, DO NOT install the unit where it is exposed to direct sunlight. If possible, make sure the unit is located far away from your neighbors’ property so that the noise from the unit will not disturb them.
Split Type Outdoor Unit (Refer to Fig 6.4, 6.5, 6.6, 6.10 and Table 6.1) Table 6.
60 cm / 24” above NOTE: The minimum distance between the outdoor unit and the walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P) (See Fig. 6.8) 30 cm / 12” ll wa n he lf w ha ts) e is acke c r n / ara ll b cm cle wa 30 ar ng (Re usi ck ” 12 m fro ba NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.
7 Refrigerant Piping Connection Safety Precautions WARNING Refrigerant Piping Connection • All field piping must be handled by a licensed technician and must comply with all local and national regulations. • If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration in the room from exceeding the safety limit in the event of refrigerant leakage.
4. Remove PVC tape from ends of pipe when ready to perform flaring work. 5. Clamp flare form onto the end of the pipe. The end of the pipe must extend beyond the flare form. NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit to prevent twisting or other damage. Flare form Fig. 7.7 Pipe Fig. 7.4 6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool clockwise until the pipe is fully flared.
8 Wiring Safety Precautions WARNING • • • • • • Wiring • • Be sure to disconnect the power supply before performing any electrical work. All electrical wiring must be in accordance with all local and national regulations. Electrical wiring must be done by a qualified technician. Improper connections may lead to electrical malfunction, injury, and fire. An independent circuit and circuit breaker must be used for this unit. DO NOT power another appliance through the same circuit breaker.
Table 8.2: European Regions Rated Current of Appliance (A) Nominal Cross-Sectional Area (mm²) 6 0.75 6 - 10 1 10 - 16 1.5 16 - 25 2.5 25- 32 4 32 - 45 6 b. Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about 15cm (6”) of the wire leads inside. c. Strip the insulation from the ends of the wire leads. d. Using a wire crimper, crimp u-lugs on the ends of the wires (Ensuring solid contact). 5. Insulate unused wires with electrical tape.
Wiring Figure CAUTION Plug the connective cables to the corresponding terminals, as shown, with their matching numbers on the terminal block of the indoor and outdoor units. For example, in the US models shown in the following diagram, Terminal (A) of the outdoor unit must connect with Terminal (A) on the indoor unit, through the same colored wire lead, without any inversions along the way.
NOTE: Please refer to the following figures if end-users wish to perform their own wiring.
Model D Five-Zone (Quint-Split) models: Model A (Newest) Wiring Model B (Some Older Models might utilize B, C, or D Model wiring) Model C Page 18 Model D
CAUTION After confirmation of the above conditions, follow these guidelines when performing wiring: • Always have an individual dedicated power circuit specifically for the air conditioner. Always follow the circuit diagram posted on the inside of the control cover. • Screws that fasten the wiring inside the casing of the electrical terminals may come lose during transporation. Because loose screws can cause wire burn-out, check that the screws are tightly fastened and that all connections are secure.
end of the refrigerant pipes. The leak must be located, and the leaking nut must be tightened properly, before re-vacuuming the circuit. 9. If the vacuum is achieved, close the manifold valve at the low (blue) side on your gauge manifold first, and shut the vacuum pump off. Leave the gauge manifold set and the hoses connected, and recheck the vacuum reading 15 minutes later to ensure there is no vacuum loss. (Very small increases in vacuum level is normal). 10. Circuit A is now dry and free of contaminants.
COMMON (MASTER) Service Valves Flare nut 3-way (Gas) Valve Cap Valve body Valve stem Circuit Service Valves 15. Power up the system, and run the indoor unit for circuit A in COOLING mode to ensure that all functions are working. 16. Switch the indoor unit of circuit A to HEAT mode, and ensure that all functions are working. 17. Set temperature on remote to the HIGHEST setting, and while the unit is running in heat mode, check one last time for leaks on all 4 related pipe connections of circuit A.
Note: The first and largest capacity indoor unit it in the reverse direction. Check your low pressure should always be connected to circuit A as primary. gauge on the manifold to verify that it now indicates 4. If the manifold gauge set’s hoses have 1/4” SAE positive pressure of approximately 80 to 120 PSI in connections, a 1/4” to 5/16” SAE port adapter will your lines. be needed. (sold separately). Manifold Gauge Low pressure gauge High pressure gauge 5.
Flare nut 3-way (gas) valve of a circuit. Cap Valve body Valve stem 18. Power up the system, and run the indoor unit for circuit A in COOLING mode to verify that all functions are working. 19. Switch the indoor unit of circuit A to HEAT mode, and verify that all functions are working. 20. Set the temperature on remote to HIGHEST setting, and while the unit is running in heat mode, check one last time for leaks at all 4 related pipe connections of circuit A.
6. Set the refrigerant container onto an electronic charging scale, and record the weight (or zero-out the scale, depending on the scale used). 7. Start all indoor units attached to the system in cooling mode, and lower the set points on each of their controllers to the minimum setting, so that the system will not shut off during the procedure. 8. Refrigerant can now be added to the system.
Outdoor Unit Error Display YN020GMFI22M2D, YN030GMFI22M3D, YN040GMFI22M4D, YN050GMFI22M5D Display E0 E2 E5 E6 E8 LED STATUS Outdoor unit EEPROM parameter error Communication malfunction between indoor and outdoor units Communication malfunction between IPM board and outdoor main control board Outdoor temperature sensor (coil sensor T3,ambient sensor T4, Compressor discharge sensor T5、indoor coil outlet pipe sensor T2B) malfunction Over-voltage or under-voltage protection PFC module protection Outdoor fan
Note On Adding Refrigerant CAUTION • Refrigerant charging must be performed after wiring, vacuuming, and leak testing. DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage the unit or impact it’s functioning. • Charging with unsuitable substances may cause explosions or accidents. Ensure that only the appropriate refrigerant (R410a) is used. • Refrigerant containers must be opened slowly. Always use protective gear when charging the system.
Test Run Before Test Run A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test: a) Indoor and outdoor units are properly installed. b) Piping and wiring are properly connected. c) No obstacles near the inlet and outlet of the unit that might cause poor performance or product malfunction. d) Refrigeration system does not leak. e) Drainage system is unimpeded and draining to a safe location.
Function of Automatic Wiring/Piping Correction 11 Automatic Wiring/Piping Correction Function The newest models now feature automatic correction of wiring/piping errors. Press the "check switch" on the outdoor unit PCB board for 5 seconds until the LED displays "CE”, indicating that this function is working. Approximately 5-10 minutes after the switch is pressed, the "CE" disappears, meaning that the wiring/piping error is corrected and that all wiring/piping is properly connected.
The design and specifications of this product are subject to change without prior notice as development continues. Consult with the sales agency or manufacturer for details. is a registered trademark of Parker Davis HVAC International, Inc. Parker Davis HVAC International, Inc. 2250 NW 102 Place, Doral, FL 33172 - USA Tel : (305) 513-4488 Fax : (305) 513-4499 email : info@pd-hvac.com Website: www.pd-hvac.com Copyright 2017, Parker Davis HVAC International, Inc., All rights reserved.