Troubleshooting Guide

Table Of Contents
7.13 P6/PC 03(High pressure protection or Low pressure protection diagnosis and solution)
Description: Outdoor pressure switch cut off the system because high pressure is higher than 638 PSI or outdoor
pressure switch cut off the system because low pressure is lower than 19 PSI, the LED displays the failure code.
Recommended parts to prepare:
Connection wires
Outdoor PCB
Refrigerant
Pressure switch
Outdoor fan
Troubleshooting and repair:
Troubleshooting 35
Are the high pressure switch
and main control board wired
correctly?
Method: Disconnect the plug.
Measure the resistance of the
high pressure protector.
If the
protector is normal the value is
0. Does a problem still exist ?
Yes
Yes
No
No
Is the high pressure
protector defective?
Is the outdoor ambient
temperature higher than
122°F ?
No
Yes
Check if the outdoor unit
ventilation is good
Yes
Is the heat exchanger dirty ?
No
Yes
Replace outdoor main board.
Is the problem resolved?
No
High pressure protection
Is the outdoor fan running
properly ?
No
Yes
NO
Connect high pressure switch
and main control board
Replace high pressure protector
Ensure that the outdoor unit
ventilation is configured properly
Clean the heat exchanger
Check whether the refrigerant
system is functioning properly
Stop the unit until temps drop
Please refer to the solution of the
“Fan Speed is operating outside of
normal range” malfunction.
(continued on next page)