Troubleshooting Guide

Table Of Contents
7.9 P0/PC 00(IPM malfunction or IGBT over-strong current protection diagnosis and solution)
Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the LED displays the
failure code and the AC turns off.
Recommended parts to prepare:
Connection wires
IPM module board
Outdoor fan assembly
Compressor
Outdoor PCB
Troubleshooting and repair:
Check the wiring between
PCB and compressor.
Does an error exist?
Ensure proper connections or
replace the wires and connectors.
YES
NO
Are the IPM terminal
resistance uniform?
Replace the IPM board or
replace the outdoor PCB.
NO
Check the outdoor fan and the
outdoor unit ventilation.
YES
Is it in working order?
Please refer to the solution of
the
fan
speed is operating outside of the
normal range malfunction.
NO
Check the compressor
resistance values.
YES
Are they uniform?
Replace the compressor.
Replace the outdoor PCB.
YES
NO
Check if the IPM is
installed correctly.
YES
NO
Correct the installation, tighten the
screws and apply silicon grease
IPM continuity check
Troubleshooting 30
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.