7.4 E3/EH 03 / F5/EC 07 (Fan speed is operating outside of normal range diagnosis and
solution)
Description: When indoor / outdoor fan speed keeps too low or too high for a certain time, the LED displays the
failure code and the AC turns off.
Recommended parts to prepare:
Connection wires
Fan assembly
Fan motor
PCB
Troubleshooting and repair:
YES
Power off, then restart the unit after 2 minutes.
Is it within normal parameters?
Replace the fan motor
Does a problem remain?
The unit is operating normally NO
Shut off the power supply,
rotate the fan by hand.
YES
Does it turn easily?
Find the cause of the problem and resolve it NO
Check the wiring of fan motor.
YES
Is it improperly wired?
Ensure proper connections
Measure the voltage for
the fan motor from the PCB.
YES
Replace the main PCB
NO
Troubleshooting 23
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.