Troubleshooting Guide

Table Of Contents
Low pressure protection
Are the low pressure protector
and main control board wired
properly ?
Yes
Yes
Replace outdoor main board.
Does a problem still exist ?
No
No
Is the low pressure
protector defective?
Is the outdoor ambient
temperature too low ?
No
Yes
No
Is the valve core of the high
pressure valve fully opened?
Is the indoor fan running
properly in cooling mode ?
No
Yes
Yes
No
Check whether the refrigerant
system is functioning properly.
When the level of refrigerant is not
sufficient, does the system function
properly after more refrigerant is added?
No
Reconnect the low pressure protector
and main control board
Replace low pressure protector
Open the valve core of the high
pressure valve
Troubleshooting 36
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Method: Disconnect the plug.
Measure the resistance of the
low pressure protector. If the
protector is normal the value is
0. Does a problem still exist ?
Stop the unit until temps rise
Please refer to the solution of the
“Fan Speed is operating outside of
normal range” malfunction.