Troubleshooting Guide

Table Of Contents
7.11 P2/PC 02(High temperature protection of IPM module or High pressure protection
diagnosis and solution)
Description: If the temperature of IPM module is higher than a certain value, the LED displays the failure code.
For some models with high pressure switch, outdoor pressure switch cut off the system because high pressure
is higher than 638 PSI, and then the LED displays the failure code.
Recommended parts to prepare:
Connection wires
Outdoor PCB
(continued on next page)
IPM module board
High pressure protector
System blockages
Troubleshooting and repair:
Are they
fixed tightly?
Replace the outdoor
control PCB.
Tighten the screws and apply
silicon grease.
NO
YES
Troubleshooting 32
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Check the fastening screws on
the PCB and IPM radiator.