Full Product Manual
8. WIRING DIAGRAM
8.3 Common wiring
Recommended wire size
● Use cooper power supply wires.
● Follow local codes and regulations when select field wires, and all the above are the minimum
wire size.
● When transmitting cable length is longer than 262ft. (80m), a larger wire size should be selected.
● Install main switch and ELB for each system separately. Select the high response type ELB that
acts within 0.1second.
Max. Running Current (A): REFER TO NAMEPLATE
NOTE:
Model
(Capacity)
Power Supply
ELB
Power Source
Cable Size
Transmitting
Cable Size
Rated Current
(A)
Nominal Sensitive
Current (mA)
24K 208/230V ~/60Hz 25 30 3×12AWG 4×16AWG
36K 208/230V ~/60Hz 35 30 3×10AWG 4×16AWG
60K 208/230V ~/60Hz 60 30 3×8AWG 4×16AWG
33