5.2 Piping length correction factor
The correction factor is based on the equivalent piping length in meters (EL)
and the height difference between outdoor and indoor units in meters (H).
H:
Height difference between indoor unit and outdoor unit (m).
• H>0: Position of
outdoor unit is higher than position of indoor unit (m).
• H<0: Position of outdoor unit is lower than position of indoor unit (m).
L:
Actual one-way pi
ping length between indoor unit and outdoor unit (m).
EL: Equivalent one-way piping length between indoor unit and outdoor unit (m).
Cooling
EL[ft(m]
Model
25(7.6) 246(75)
36K/60K
1.0 0.98
0.97 0.93 0.89 0.86
0.82
0.81
0.75
0.69
38(
10)
50(15
)
75(
23
)
100
(
30)
125(38)
150(45)
164(50)
200(61)
Heating
EL[ft(m]
Model
25(7.6) 246(75)
36K/60K
1.0
0.98
0.97 0.93 0.89 0.86
0.83
0.81
0.76
0.70
38(10)
50(15)
75(23)
100(30)
125(38)
150(45)
164(50)
200(61)
24K
1.0 0.95
0.93 0.89 0.85 0.81
0.78
0.75
--
--
24K
1.0
0.94
0.93 0.89 0.85 0.81
0.78
0.75
--
--
Pipe length L
Height difference H
Indoor unit
Outdoor unit
Model
Max. Pipe
length (L)
Max. Height
difference
(H)
Add.
Refrigerant
[exceed 25ft
7.6m]
24K 164ft. (50m) 98ft. (30m)
0.38(oz/ft)
[35(g/m)]
36K 246ft. (75m) 98ft. (30m)
0.38(oz/ft)
[35(g/m)]
60K 246ft. (75m) 98ft. (30m)
0.60(oz/ft)
[56(g/m)]
9.52 (3/8') 12.7 (1/2')
15.88 (5/8') 19.05 (3/4')
Gas Diameter
90° Elbow
0.15 0.2 0.25 0.35 0.40
(mm/inch)
22.22 (7/
8')
17