16.CHECKING COMPONENTS
DC Inverter
&
Controller
Thermal Sensor
Compressor
Power
Test in resistance.
TOOL: Multi-meter.
Test the resistance of the winding. The compressor fails if the resistance of winding is 0
(short circuit)or∞(open circuit).
Familiar error:
1) Compressor motor lock.
2) Discharge pressure value approaches static pressure value.
3) Compressor motor winding abnormality.
NOTE
1) Don’t put a compressor on its side or turn over.
2) Please assemble t
he compressor in your air conditioner rapidly after removing the plugs.
Don’t place the comp. in air for a long time.
3) Avoid compressor running in reverse caused by connecting electrical wire incorrectly.
4) Warning! In case AC voltage is impressed to compressor, the compressor performance will
decrease because of its rotor magnetic force decreasing.
3. Inductance
Familiar error:
1Sound abnormality
2Insulation resistance disqualification.
Check for continuity of fuse on PCB ASS’Y.
Remove the PCB ASS’Y from the electrical component box. Then pull out the fuse from the
PCB ASS’Y.Check for continuity by a multimeter as shown below.
Fuse
PCB Ass'Y
Fuse
4. Fuse