9.FIELD SETTING
Step 4:
Open the maintenance panel.
St
ep 5:
Switch the dial code (referring to outdoor wiring diagram ) O
N position on the main control board.
Step 6:
Switch on the machine power.
Step 7:
Check if “40” is displayed on the LED digital tube of the main control board.
Step 8:
When the numerals on the LED digital tube of outdoor unit count down to 0 (40 39 38 ... 0),
and “0” begins to blink, close the shut-off valve of
the gas piping with an Allen wrench in a
clockwise direction.
Step 9:
Cut off m
achine power and the procedure for recovering refrigerant is finished.
NOTE:
Be sure to switc
h back the dial after refrigerant recovery operation. If not, it will enter
refrigerant recovery mod
e again after power ON. But if the power is not off, it will not
enter refrigerant recovery mode and will run normally.
36