Owner manual
9.1 Error Management
9 Diagnostics and Troubleshooting
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
9-2
9.1Error Management9100Error Management9-Diagnose_F ehlerbehan dlung_Allg
The PSENvip continuously carries out self-tests and output tests during 
operation. If an error is discovered, the following sequence is triggered:
 An error identifier is shown on the display of the PSENvip receiver (see 
"Error messages" in this chapter)
 The error plus some additional diagnostic data is entered in a special 
data area on the PSENvip (see "DIAGNOSTICS menu" in this chapter)
 Execution of the error reaction.
The PSENvip's reaction to an error depends on the severity of that error.
9.1.1 Minor errors
Minor errors9-Diagnose_Fehlerbehandlung_leichte_Fehler
Possible causes
 Feasibility error
 Internal error
Reaction of the PSENvip
 The PSENvip switches to a HOLD state.
 Outputs OSSD1/OSSD2 on the receiver are switched off.
 In this state it is possible to make adjustments during initial commis-
sioning and after a tool change.
Remedy
 Note the error message (see section entitled "Error messages").
 Rectify the error.
 Press the <ESC> key and return the PSENvip to the NORMAL OPER-
ATION state.
9.1.2 Major errors
Major errors9-Diagnose_Fehlerbehandlung_schwere_Fehler
Possible causes
 Serious internal error
 Wiring error, short across contacts, short circuit
 No valid tool data
 Overrun not entered
 Fault on the optical system
Reaction of the PSENvip
 The PSENvip switches to a STOP state.
 Outputs OSSD1/OSSD2 on the receiver are switched off.
 In this state, operation is no longer possible. However, diagnostics 
are available.