7.4 Enter overrun
7 Commissioning
7.4Enter overrun7400Enter overrun7-Inbetriebnahme_Nachlaufweg_eingeben_P_Variante_1
The max. overrun is a press brake variable that will depend on the ma-
chine type. Once the closing movement has stopped, the max. overrun 
must not be exceeded.
The overrun is entered during configuration via the keypad on the PSEN-
vip receiver.
Funktion_Nachlaufweg_P_Variante
Normally, the factory-assigned overrun is sufficient and does not have 
to be configured.
Funktion_Nachlaufweg_Warnung_3
Inbetriebnahme_Nachlaufweg_eingeben_P_Variante_2
To enter the overrun, follow the instructions below:
 Switch off the voltage to the PSENvip.
 Press the <ESC> + <ENTER> keys and keep them held down.
 Switch the supply voltage back on.
 Release the <ESC> + <ENTER> keys when Password? appears on 
the display.
 Enter the password within 10 s.
To do this, press the following keys in the specified sequence: 1.  , 
2.  , 3. , 4. .
The menu for entering the overrun will appear.
NOTICE
The overrun may only be entered by the press brake manufac-
turer or suitably authorised persons.
WARNING!
If you require a different overrun path than the factory-set path, 
then use the value indicated by the manufacturer on the name-
plate of the press brake, or a higher value.
If you enter a lower value for the overrun, the protected field will 
also be reduced to an unpermitted level.
Failure to comply could result in a hazardous situation, which 
could lead to serious injury and death.