User guide

PSEN op4B Series Operating Manual
50
8 REGULAR CHECKS AND MAINTENANCE
Qualified personnel must carry out the following checks regularly.
Ensure that:
The “SAFE/BREAK” LED is constantly red when you pass the test
rod from top to bottom along the length of the whole sensing area,
at any distance from either unit.
The safety light curtain switches to an OFF state when the
test/reset button is operated (“SAFE/BREAK” LED lights up red -
OSSD outputs open - monitored machine switches to a safe
condition).
The reaction time at a machine stop, incl. the reaction time of the
safety light curtain and the machine overrun time, is within the
limits defined through the calculation of the safety distance (see
Chapter 2 “Installation”).
The minimum safety distance between the danger zone and the
protected field is in accordance with the details stated in Chapter 2
Installation”.
Nobody can access and remain in the danger zone between the
safety light curtains and the hazardous machine parts.
The danger zone cannot be accessed from any unprotected area.
There is no visible damage to the safety light curtain and/or the
external electrical connections.
We recommend a yearly inspection.