PNOZ s8 Safety relays Operating Manual-21400-EN-07
Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
PNOZ s8 Safety relay PNOZ s8 The unit meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1. The contact expansion module is used to increase the number of instantaneous safety contacts available on a base unit. Base units are all safety relays with feedback loop monitoring. The category that can be achieved in accordance with EN ISO 13849-1 depends on the category of the base unit. The contact expansion module may not exceed this.
PNOZ s8 Block diagram/terminal configuration Centre: Front view with cover, right: Front view without cover Function description with PNOZsigma base unit: } Dual-channel operation via PNOZsigma connector without PNOZsigma base unit: } Single-channel operation: one input circuit affects the output relays Installation Install contact expansion module without base unit: } Ensure that the plug terminator is inserted at the sid
PNOZ s8 Wiring Please note: } Information given in the "Technical details" must be followed. } The outputs 13-14, 23-24 are safety contacts. } Semiconductor output Y32 should not be used for safety circuits! } To prevent contact welding, a fuse should be connected before the output contacts (see technical details). } Calculation of the max. cable length lmax in the input circuit: Rlmax = max.
PNOZ s8 } } Feedback loop – with PNOZsigma base unit: The feedback loop is connected and evaluated via the connector. – without PNOZsigma base unit: Feedback loop does not need to be monitored because the contact expansion block monitors its own output contacts. Semiconductor output *Connect together the 0V connections on all the external power supplies Information If a base unit and a contact expansion module from the PNOZsigma range are linked via the connector, no additional wiring is necessary.
PNOZ s8 Error indicators Fault Diagnostics: Internal error, unit defective } Remedy: Switch supply voltage off and then on again, change unit if necessary. Faults - malfunctions } Contact malfunctions: If the contacts have welded, reactivation will not be possible after the input circuit has opened. Technical details General Approvals Electrical data Supply voltage Voltage Type Voltage tolerance Output of external power supply (DC) Residual ripple DC Continuous duty Max.
PNOZ s8 Relay outputs Max. short circuit current IK Utilisation category In accordance with the standard Safety contacts, AC1 at Max. current Min. current Max. power Safety contacts, DC1 at Max. current Min. current Max. power Utilisation category In accordance with the standard Safety contacts, AC15 at Max. current Safety contacts, DC13 (6 cycles/ min) at Max.
PNOZ s8 Environmental data Climatic suitability Ambient temperature Temperature range Storage temperature Temperature range EMC Vibration In accordance with the standard Frequency Max. amplitude Airgap creepage In accordance with the standard Overvoltage category Pollution degree Rated insulation voltage Rated impulse withstand voltage Protection type Mounting (e.g.
PNOZ s8 Mechanical data Dimensions Height Width Depth Weight 750108 751108 98,0 mm 12,5 mm 120,0 mm 105 g 100,0 mm 12,5 mm 120,0 mm 105 g The standards current on 2009-12 apply. Safety characteristic data Operating mode EN ISO 13849-1: 2006 PL Safety con- PL c tacts, instantaneous EN ISO 13849-1: 2006 Category Cat.
PNOZ s8 Order reference Order reference Product type Features Terminals Order no. 750 108 PNOZ s8 24 VDC Screw terminals PNOZ s8 C 24 VDC Spring-loaded terminals 751 108 EC declaration of conformity This product/these products meet the requirements of the directive 2006/42/EC for machinery of the European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co.
In many countries we are represented by our subsidiaries and sales partners. ... Please refer to our homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www.pilz.com Technical support +49 711 3409-444 support@pilz.