Owner manual
PNOZ s7
Operating Manual PNOZ s7
21399-EN-09
9
Relay outputs 750107 751107 751187
Safety contacts, DC1
at
24 V 24 V 24 V
Max. current 6,0 A 6,0 A 6,0 A
Min. current 0,01 A 0,01 A 0,01 A
Max. power 150 W 150 W 150 W
Utilisation category
In accordance with the
standard
EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Auxiliary contacts,
AC15 at
230 V 230 V 230 V
Max. current 2,0 A 2,0 A 2,0 A
Auxiliary contacts,
DC13 (6 cycles/min) at
24 V 24 V 24 V
Max. current 2,0 A 2,0 A 2,0 A
Safety contacts, AC15
at
230 V 230 V 230 V
Max. current 5,0 A 5,0 A 5,0 A
Safety contacts, DC13
(6 cycles/min) at
24 V 24 V 24 V
Max. current 5,0 A 5,0 A 5,0 A
Contact fuse protection,
external safety contacts
In accordance with the
standard
EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Circuit breaker,
24V AC/DC, character-
istic B/C
6 A 6 A 6 A
Contact fuse protection,
external auxiliary contacts
Blow-out fuse, quick 4 A 4 A 4 A
Blow-out fuse, slow 2 A 2 A 2 A
Circuit breaker, 24
V AC/DC, characteristic
B/C
2 A 2 A 2 A
Contact material AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au AgCuNi + 0,2 µm Au
Conventional thermal
current while loading
several contacts
750107 751107 751187
Ith per contact at UB DC
Conv. therm. current
with 1 contact
6,00 A 6,00 A 6,00 A
Conv. therm. current
with 2 contacts
5,50 A 5,50 A 5,50 A
Conv. therm. current
with 3 contacts
4,50 A 4,50 A 4,50 A
Conv. therm. current
with 4 contacts
4,00 A 4,00 A 4,00 A