Manual

PNOZ s6
Operating Manual PNOZ s6
21398-EN-08
12
Semiconductor
outputs
750106 750136 751106 751136
Number 1 1 1 1
Voltage 24,0 V 24,0 V 24,0 V 24,0 V
Current 20 mA 20 mA 20 mA 20 mA
Relay outputs 750106 750136 751106 751136
Max. short circuit
current IK
1 kA 1 kA 1 kA 1 kA
Utilisation category
In accordance
with the standard
EN 60947-4-1 EN 60947-4-1 EN 60947-4-1 EN 60947-4-1
Auxiliary contacts,
AC1 at
240 V 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A 0,01 A
Max. current 6,0 A 6,0 A 6,0 A 6,0 A
Max. power 1500 VA 1500 VA 1500 VA 1500 VA
Auxiliary contacts,
DC1 at
24 V 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A 0,01 A
Max. current 6,0 A 6,0 A 6,0 A 6,0 A
Max. power 150 W 150 W 150 W 150 W
Safety contacts,
AC1 at
240 V 240 V 240 V 240 V
Max. current 6,0 A 6,0 A 6,0 A 6,0 A
Min. current 0,01 A 0,01 A 0,01 A 0,01 A
Max. power 1500 VA 1500 VA 1500 VA 1500 VA
Safety contacts,
DC1 at
24 V 24 V 24 V 24 V
Max. current 6,0 A 6,0 A 6,0 A 6,0 A
Min. current 0,01 A 0,01 A 0,01 A 0,01 A
Max. power 150 W 150 W 150 W 150 W
Utilisation category
In accordance
with the standard
EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Auxiliary contacts,
AC15 at
230 V 230 V 230 V 230 V
Max. current 5,0 A 3,0 A 5,0 A 3,0 A
Auxiliary contacts,
DC13 (6 cycles/
min) at
24 V 24 V 24 V 24 V
Max. current 5,0 A 4,0 A 5,0 A 4,0 A
Safety contacts,
AC15 at
230 V 230 V 230 V 230 V
Max. current 5,0 A 3,0 A 5,0 A 3,0 A
Safety contacts,
DC13 (6 cycles/
min) at
24 V 24 V 24 V 24 V
Max. current 5,0 A 4,0 A 5,0 A 4,0 A