User guide

PNOZ s5
Operating Manual PNOZ s5
21397-EN-09
7
Set operating modes
} Switch off supply voltage.
} Select operating mode via the operating mode selector switch "mode".
} If the operating mode selector switch "mode" is in its start position (vertical position), an
error message will appear.
Operating mode
selector switch
"mode"
Automatic/man-
ual start
Monitored start
rising edge
Monitored start
falling edge
Automatic start
with start-up test
Without detec-
tion of shorts
across contacts








With detection of
shorts across
contacts








Set delay time
Time selector switch "t[s]"
Factor selector switch "n"
n x t[s] = Delay time
Example:
t = 4 s, n = 5
Delay time = 5 x 4 = 20 s
Connection
} Supply voltage
Supply voltage AC DC







} Input circuit
Input circuit Single-channel Dual-channel
E-STOP
without detection of shorts
across contacts








E-STOP
with detection of shorts
across contacts




