User guide
PNOZ s5
Operating Manual PNOZ s5
21397-EN-09
15
Relay outputs 750105 750135 751105 751135 751185
Safety con-
tacts, delayed:
DC1 at
24 V 24 V 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A 0,01 A 0,01 A
Max. current 6,0 A 6,0 A 6,0 A 6,0 A 6,0 A
Max. power 150 W 150 W 150 W 150 W 150 W
Safety con-
tacts, AC1 at
240 V 240 V 240 V 240 V 240 V
Max. current 6,0 A 6,0 A 6,0 A 6,0 A 6,0 A
Min. current 0,01 A 0,01 A 0,01 A 0,01 A 0,01 A
Max. power 1500 VA 1500 VA 1500 VA 1500 VA 1500 VA
Safety con-
tacts, DC1 at
24 V 24 V 24 V 24 V 24 V
Max. current 6,0 A 6,0 A 6,0 A 6,0 A 6,0 A
Min. current 0,01 A 0,01 A 0,01 A 0,01 A 0,01 A
Max. power 150 W 150 W 150 W 150 W 150 W
Utilisation cate-
gory
In accordance
with the
standard
EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Safety con-
tacts, delayed:
AC15 at
230 V 230 V 230 V 230 V 230 V
Max. current 3,0 A 3,0 A 3,0 A 3,0 A 3,0 A
Safety con-
tacts, delayed:
DC13 (6 cy-
cles/min) at
24 V 24 V 24 V 24 V 24 V
Max. current 4,0 A 4,0 A 4,0 A 4,0 A 4,0 A
Safety con-
tacts, AC15 at
230 V 230 V 230 V 230 V 230 V
Max. current 3,0 A 3,0 A 3,0 A 3,0 A 3,0 A
Safety con-
tacts, DC13 (6
cycles/min) at
24 V 24 V 24 V 24 V 24 V
Max. current 4,0 A 4,0 A 4,0 A 4,0 A 4,0 A
Contact fuse pro-
tection, external
safety contacts
In accordance
with the
standard
EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Blow-out fuse,
quick
6 A 6 A 6 A 6 A 6 A
Blow-out fuse,
slow
4 A 4 A 4 A 4 A 4 A
Circuit break-
er, 24V AC/
DC, charac-
teristic B/C
4 A 4 A 4 A 4 A 4 A