User guide
PNOZs4
OperatingManualPNOZs4
21396EN13
23
Conventionalthermalcurrent
whileloadingseveralcontacts
751134 751184
IthpercontactatUBAC
Conv.therm.currentwith1con
tact 6,00A –
Conv.therm.currentwith2con
tacts 6,00A –
Conv.therm.currentwith3con
tacts 4,50A –
IthpercontactatUBDC
Conv.therm.currentwith1con
tact 6,00A 6,00A
Conv.therm.currentwith2con
tacts 6,00A 6,00A
Conv.therm.currentwith3con
tacts 4,50A 5,00A
Times 751134 751184
Switchondelay
Withautomaticstarttyp. 170ms 170ms
Withautomaticstartmax. 300ms 300ms
Withautomaticstartafterpower
ontyp. 350ms 350ms
Withautomaticstartafterpower
onmax. 600ms 600ms
Withmanualstarttyp. 40ms 40ms
Withmonitoredstartwithrising
edgetyp. 35ms 35ms
Withmonitoredstartwithrising
edgemax. 50ms 50ms
Withmonitoredstartwithfalling
edgetyp. 55ms 55ms
Withmonitoredstartwithfalling
edgemax. 70ms 70ms
Delayondeenergisation
WithESTOPtyp. 10ms 10ms
WithESTOPmax. 20ms 20ms
Withpowerfailuretyp. – 40ms
Withpowerfailuremax. – 80ms
Withpowerfailuretyp.UB240V 300ms –
Withpowerfailuremax.UB240
V 450ms –
Recoverytimeatmax.switching
frequency1/s
AfterESTOP 50ms 100ms
Afterpowerfailure 100ms 100ms
Waitingperiodwithamonitored
start
Withrisingedge 120ms 120ms
Withfallingedge 150ms 250ms