User guide
PNOZs4
OperatingManualPNOZs4
21396EN13
22
Relayoutputs 751134 751184
Utilisationcategory
Inaccordancewiththestandard EN6094741 EN6094741
Auxiliarycontacts,AC1at 240V 240V
Min.current 0,01A 0,01A
Max.current 6,0A 6,0A
Max.power 1500VA 1500VA
Auxiliarycontacts,DC1at 24V 24V
Min.current 0,01A 0,01A
Max.current 6,0A 6,0A
Max.power 150W 150W
Safetycontacts,AC1at 240V 240V
Max.current 6,0A 6,0A
Min.current 0,01A 0,01A
Max.power 1500VA 1500VA
Safetycontacts,DC1at 24V 24V
Max.current 6,0A 6,0A
Min.current 0,01A 0,01A
Max.power 150W 150W
Utilisationcategory
Inaccordancewiththestandard EN6094751 EN6094751
AuxiliarycontactsAC15at 230V 230V
Max.current 3,0A 5,0A
Auxiliarycontacts,DC13(6
cycles/min)at 24V 24V
Max.current 4,0A 5,0A
Safetycontacts,AC15at 230V 230V
Max.current 3,0A 5,0A
SafetycontactsDC13(6cycles/
min)at 24V 24V
Max.current 4,0A 5,0A
Contactfuseprotectionexternal,
safetycontacts
Inaccordancewiththestandard EN6094751 EN6094751
Blowoutfuse,quick 6A 10A
Blowoutfuse,slow 4,00A 6,00A
Circuitbreaker,24VAC/DC,
characteristicB/C 4A 6A
Contactfuseprotectionexternal,
auxiliarycontacts
Blowoutfuse,quick 6A 10A
Blowoutfuse,slow 4A 6A
Circuitbreaker,24VAC/DC,
characteristicB/C 4A 6A
Contactmaterial AgCuNi+0,2µmAu AgCuNi+0,2µmAu