Error
no. Error message Description Remedy
10256 Ini pnp pnp
both inactive
Both proximity
switches are inactive
at the same time
-Install proximity switches such
that one proximity switch is al-
ways activated.
-Ensure that the encoders are
configured correctly
-Ensure that the proximity
switches operate correctly
-Ensure that the supply voltage
is present at the proximity
switches
Ensure that the proximity switch-
es are wired correctly
10257 Ini npn npn
both inactive
Both proximity
switches are inactive
at the same time
-Install proximity switches such
that one proximity switch is al-
ways activated.
-Ensure that the encoders are
configured correctly
-Ensure that the proximity
switches operate correctly
-Ensure that the supply voltage
is present at the proximity
switches
Ensure that the proximity switch-
es are wired correctly
10258 Ini pnp npn
both inactive
Both proximity
switches are inactive
at the same time
-Install proximity switches such
that one proximity switch is al-
ways activated.
-Ensure that the encoders are
configured correctly
-Ensure that the proximity
switches operate correctly
-Ensure that the supply voltage
is present at the proximity
switches
Ensure that the proximity switch-
es are wired correctly
10259 Ini npn pnp
both inactive
Both proximity
switches are inactive
at the same time
-Install proximity switches such
that one proximity switch is al-
ways activated.
-Ensure that the encoders are
configured correctly
-Ensure that the proximity
switches operate correctly
-Ensure that the supply voltage
is present at the proximity
switches
Ensure that the proximity switch-
es are wired correctly