Owner's manual

Commissioning
Operating Manual PNOZ s30
1001715-EN-13
38
EMC-compliant wiring for connecting 2 proximity switches



















To avoid EMC interference we recommend that the shield on the encoder cables or the
housing of the shielded junction box is only connected to earth at a single point:
A or B or C or D or E
Conductor loops outside the shield must be avoided.
If a shielded junction box is not used, the shield must run continuously from the encoder to
the evaluation device.
Display menu - Configuration
The menu settings are made on the unit's display via a rotary knob. You have the option to
make the settings on the knob by hand or with a screwdriver. If you make the settings with
a screwdriver, the knob can remain within the unit.
6.2