Owner's manual

Function description
Operating Manual PNOZ s30
1001715-EN-13
26
Proximity switch assembly:


Example pnp – pnp:
Proximity switch 1
Proximity switch 2
Energised
De-energised
Energised
De-energised
> 1 % of the period length
ATTENTION!
Appropriate installation measures should be taken to prevent a foreign body
coming between the signal encoder and the proximity switch. If not, the for-
eign body could cause invalid signals.
} Please note the values stated in the technical details
} The maximum frequency of the used encoders must be entered for a complete configu-
ration ("Encoder" Menu -> "Track AB" -> "Track AB fmax" / "Track Z" -> "Track Z
fmax").
Rotary encoders
} The following rotary encoders can be used:
TTL, HTL (single-ended or differential signals)
sin/cos 1 Vss
– Hiperface
} The rotary encoders can be connected with or without Z index (0 index)
} The cable used to connect the rotary encoders must be shielded (see connection dia-
grams in the chapter entitled "EMC-compliant wiring").
} A proximity switch can also be connected to track Z for monitoring broken shearpins
} Track S can be used:
To connect an encoder's error output
To monitor voltages between 0 V and 30 V for a permitted upper and lower limit.
For example, the encoder's supply voltage can be monitored.