Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received. Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
PNOZ s2 PNOZ s2 safety relay The safety relay provides a safety-related interruption of a safety circuit. The safety relay meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1 and may be used in applications with } E-STOP pushbuttons } Safety gates For your safety } Only install and commission the unit if you have read and understood these operating instructions and are familiar with the applicable regulations for health and safety at work and accident prevention.
PNOZ s2 Safety features The relay meets the following safety requirements: } The circuit is redundant with built-in self-monitoring. } The safety function remains effective in the case of a component failure. } The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. } The unit has an electronic fuse.
PNOZ s2 Installation Install base unit without contact expansion module: } Ensure that the plug terminator is inserted at the side of the unit. Connect base unit and PNOZsigma contact expansion module: } Remove the plug terminator at the side of the base unit and at the contact expansion module. } Connect the base unit and the contact expansion module to the supplied connector before mounting the units to the DIN rail.
PNOZ s2 Preparing for operation Operating modes The operating mode is set via the rotary switch on the unit. You can do this by opening the cover on the front of the unit. CAUTION! Do not adjust the rotary switch during operation, otherwise an error message will appear, the safety contacts will open and the unit will not be ready for operation until the supply voltage has been switched off and then on again. Set operating modes } Switch off supply voltage.
PNOZ s2 } Input circuit Input circuit Single-channel Emergency stop without detection of shorts across contacts Safety gate without detection of shorts across contacts } Dual-channel Start circuit/feedback loop Start circuit/feedback loop Start circuit Feedback loop Automatic start Manual/monitored start } Semiconductor output *Connect together the 0V co
PNOZ s2 Operation The unit is ready for operation when the Power LED is permanently lit. LEDs indicate the status and errors during operation: LED on LED flashes Information Status indicators and error indicators may occur independently. In the case of an error display, the "Fault" LED will light or flash (exception: "Supply voltage too low"). An LED that is also flashing indicates the potential cause of the error. An LED that is lit and is static indicates a normal operating status.
PNOZ s2 Reset Fault Diagnostics: Position of rotary switch is not permitted or rotary switch was adjusted during operation. } Remedy: Switch supply voltage off and then on again. Power, In1, In2, Out, Reset, Fault Diagnostics: The operating mode selector switch "mode" is in its start position (vertical position) } Remedy: Switch off the supply voltage and set the required operating mode on operating mode selector switch "mode".
PNOZ s2 Example } Inductive load: 0,2 A } Utilisation category: AC15 } Contact service life: 2,000,000 cycles Provided the application requires fewer than 2,000,000 cycles, the PFH value (see technical details) can be used in the calculation. To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With contactors, use freewheel diodes for spark suppression.
PNOZ s2 Semiconductor outputs Number Voltage Current Relay outputs Max. short circuit current IK Utilisation category In accordance with the standard Auxiliary contacts, AC1 at Min. current Max. current Max. power Auxiliary contacts, DC1 at Min. current Max. current Max. power Safety contacts, AC1 at Max. current Min. current Max. power Safety contacts, DC1 at Max. current Min. current Max. power Utilisation category In accordance with the standard Auxiliary contacts, AC15 at Max.
PNOZ s2 Relay outputs Contact material Conventional thermal current while loading several contacts Ith per contact at UB DC Conv. therm. current with 1 contact Conv. therm. current with 2 contacts Conv. therm. current with 3 contacts Times Switch-on delay With automatic reset typ. With automatic reset max. With automatic reset after power on typ. With automatic reset after power on max. With manual reset typ. With manual reset max. With monitored reset with rising edge typ.
PNOZ s2 Environmental data Climatic suitability Ambient temperature Temperature range Storage temperature Temperature range EMC Vibration In accordance with the standard Frequency Max. amplitude Airgap creepage In accordance with the standard Overvoltage category Pollution degree Rated insulation voltage Rated impulse withstand voltage Protection type Mounting (e.g.
PNOZ s2 Mechanical data Dimensions Height Width Depth Weight 750102 751102 98,0 mm 17,5 mm 120,0 mm 175 g 100,0 mm 17,5 mm 120,0 mm 175 g The standards current on 2009-12 apply. Safety characteristic data Operating mode EN ISO 13849-1: 2006 EN ISO 13849-1: 2006 PL Category Safety con- PL e tacts, instantaneous Cat.
PNOZ s2 Order reference Order reference Product type Features Terminals Order no. 750 102 PNOZ s2 24 V DC Screw terminals PNOZ s2 C 24 V DC Spring-loaded terminals 751 102 EC declaration of conformity This product/these products meet the requirements of the directive 2006/42/EC for machinery of the European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co.
In many countries we are represented by our subsidiaries and sales partners. ... Please refer to our homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfildern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de Internet: www.pilz.com Technical support +49 711 3409-444 support@pilz.