Owner's manual
PNOZ s11
Operating Manual PNOZ s11
21693-EN-08
5
Wiring
Please note:
} Information given in the "Technical details" must be followed.
} Outputs 13-14, 23-24, 33-34, 43-44, 63-64, 73-74, 83-84, 93-94 are safety contacts;
output 51-52 is an auxiliary contact (e.g. for display).
} Auxiliary contact 51-52 should not be used for safety circuits!
} To prevent contact welding, a fuse should be connected before the output contacts (see
technical details).
} Calculation of the max. cable length l
max
in the input circuit:
R
lmax
= max. overall cable resistance (see technical details)
R
l
/ km = cable resistance/km
} Use copper wire that can withstand 60/75 °C.
} Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.
Preparing for operation
} Supply voltage
Supply voltage AC DC
} Input circuit
Input circuit Single-channel Dual-channel
Base unit:
Safety relay PNOZ X
Base unit:
PNOZelog safety relay
Driven via semiconductor
outputs (24 VDC)