User Manual

PNOZ s10
Operating Manual PNOZ s10
21402-EN-08
5
Wiring
Please note:
} Information given in the "Technical details" must be followed.
} Outputs 13-14, 23-24, 33-34, 43-44 are safety contacts; outputs 51 -52 are auxiliary
contacts (e.g. for display).
} Auxiliary contact 51-52 should not be used for safety circuits!
} To prevent contact welding, a fuse should be connected before the output contacts (see
technical details).
} Calculation of the max. cable length l
max
in the input circuit:





R
lmax
= max. overall cable resistance (see technical details)
R
l
/ km = cable resistance/km
} Use copper wire that can withstand 60/75 °C.
} Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.
} Do not connect undesignated terminals.
} The power supply must comply with the regulations for extra low voltages with safe
electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.
Preparing for operation
} Supply voltage
Supply voltage AC DC







} Input circuit
Input circuit Single-channel Dual-channel
Base unit:
Safety relay PNOZ X







Base unit:
Safety relay PNOZelog
Driven via semiconductor
outputs
(24 VDC)






