5
Installation
Install base unit without contact expansion module:
} Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module:
} Remove the plug terminator at the side of the base unit and at the contact expansion
module.
} Connect the base unit and the contact expansion module to the supplied connector be-
fore mounting the units to the DIN rail.
Installation in control cabinet
} The safety relay should be installed in a control cabinet with a protection type of at least
IP54.
} Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
} When installed vertically: Secure the unit by using a fixing element (e.g. retaining brack-
et or end angle).
} Push the device upwards or downwards before lifting it from the DIN rail.
Wiring
Please note:
} Information given in the "Technical details" must be followed.
} The outputs 13-14, 23-24 are safety contacts.
} Semiconductor output Y32 should not be used for safety circuits!
} To prevent contact welding, a fuse should be connected before the output contacts (see
technical details).
} Calculation of the max. cable length l
max
in the input circuit:
R
lmax
= max. overall cable resistance (see technical details)
R
l
/ km = cable resistance/km
} Use copper wire that can withstand 60/75 °C.
} Sufficient fuse protection must be provided on all output contacts with capacitive and in-
ductive loads.